GE Fanuc IC200PWR002G Expanded Power Supply Module
GE Fanuc IC200PWR002G Expanded Power Supply Module
GE Fanuc IC200PWR002G Expanded Power Supply Module
/ 3

GE Fanuc IC200PWR002G Expanded Power Supply Module

  • Manufacturer: GE Fanuc

  • Part Number: IC200PWR002G

  • Condition:New with Original Package

  • Product Type: Power Supply Modules

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

GE IC200PWR002G VersaMax Expanded Power Supply Module

Configured for backplane logic power distribution in VersaMax PLC networks, the GE IC200PWR002G (IC200PWR002 VersaMax Expanded Power Supply Module) provides direct physical/electrical execution.

Hardware Specifications

Parameter Specification
Model IC200PWR002G
Brand GE Fanuc
Origin USA
Weight 0.12 kg (Shipping weight 2.0 kg)
Dimensions 49 mm W x 133.4 mm H x 39 mm D
Operating Temp 0 to 60 deg C
Power Consumption 11 W input power
Input Voltage Range 18 to 30 VDC (24 VDC nominal)
Output Voltage 3.3 VDC and 5 VDC backplane supply
Total Output Current 1.5 A maximum
3.3V Output Current 0.25 A maximum (Up to 1.0 A depending on load configuration)
5V Output Current 1.5 A minus 3.3V output current draw
Inrush Current 20 A at 24 VDC (6 ms), 25 A at 30 VDC (6 ms)
Hold-up Time 10 ms
Isolation 250 VAC continuous; 1500 VAC for 1 min (field-to-logic/frame ground)
Mounting DIN rail or panel mount via expansion carrier
Protection Features Short circuit, overload, reverse polarity
Status Indicators 1 green PWR LED
Terminal Block 5 screw-clamp terminals (DC+, DC-, GND, 2 unused)
Humidity 5% to 95% (non-condensing)
Certifications UL, CE, CSA, Class I Div 2 Groups A-D, Class 1 Zone 2

Backplane Bus Communication Velocity and System Architecture

The IC200PWR002G integrates directly with the VersaMax backplane bus architecture, ensuring regulated voltage rails feed all connected CPU, NIU, and local I/O modules without voltage sag. Maintain deterministic communication velocity across extended racks by placing booster supplies wherever backplane current budgets exceed local capacity. Furthermore, the unit supports hot-swap operations during continuous system run-states while preserving firmware flash compatibility across legacy and modern VersaMax platforms.

Frequently Asked Questions

Q: How is the total 1.5 A output current budget split between the 3.3 VDC and 5 VDC rails?

A: The total combined output current must not exceed 1.5 A. The 5 VDC rail current capacity equals 1.5 A minus the current drawn by the 3.3 VDC rail.

Q: Does the IC200PWR002G module support hot-swapping during active operation?

A: Yes. The module features integrated hot-swap execution capability, permitting field replacement without requiring system shutdown or power isolation of adjacent backplane carriers.

Q: What are the strict grounding requirements for the DC input terminals?

A: The DC- terminal must connect directly to frame earth ground. Floating power configurations are unapproved because single-point isolation testing rates the field-to-logic interface at 1500 VAC for 1 minute.

Field Installation Guidelines

Mount the unit on a standard 35 mm DIN rail or panel base. Secure all 24 VDC power connections using the 5-point screw-clamp terminal block, ensuring that DC- ties directly to cabinet frame ground. Maintain proper spacing to allow natural convection cooling across the housing, and verify that the total backplane current load of downstream I/O modules remains below the 1.5 A maximum output rating.