{"product_id":"ge-fanuc-ic200udr005-ba-versamax-micro-plc-controller","title":"GE Fanuc IC200UDR005-BA VersaMax Micro PLC Controller","description":"\u003ch2\u003eGE Fanuc IC200UDR005-BA VersaMax Micro Controller\u003c\/h2\u003e\n\u003cp\u003eThe \u003cstrong\u003eGE Fanuc IC200UDR005-BA\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003eIC200UDR005BA\u003c\/strong\u003e Micro PLC Controller, operates as a dedicated hardware component for centralized logic processing and field I\/O execution within GE VersaMax system platforms. The unit integrates a 32-bit microprocessor, internal AC power conversion circuitry, and fixed discrete terminal points into a single housing. Field technicians route field wiring directly to the terminal block interface, allowing the internal CPU to read 16 DC input channels and drive 12 discrete relay outputs according to program logic stored in non-volatile memory.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eIC200UDR005-BA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eGE Fanuc\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eJapan\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.6 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e15.2 x 8.9 x 7.6 cm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eIntegrated AC power supply (120\/240 VAC input)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eArchitecture\u003c\/td\u003e\n\u003ctd\u003e32-bit microprocessor\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eUser Memory\u003c\/td\u003e\n\u003ctd\u003e12 KB Program Memory, 6 KB Register Memory\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIntegrated I\/O\u003c\/td\u003e\n\u003ctd\u003e28 points (16 DC inputs, 12 relay outputs rated 2 A per point)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSerial Ports\u003c\/td\u003e\n\u003ctd\u003eDual RS-232 and RS-485 interfaces\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNetwork Protocols\u003c\/td\u003e\n\u003ctd\u003eSNP Slave, Modbus RTU Slave\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTariff Code (HS Code)\u003c\/td\u003e\n\u003ctd\u003e8537109060\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eDeterministic Network Connectivity \u0026amp; I\/O Density Scaling\u003c\/h3\u003e\n\u003cp\u003eThe internal processor manages serial communication over RS-232 and RS-485 interfaces, executing Modbus RTU Slave and SNP protocols without compromising scan time performance. Control engineers expand total I\/O density scaling by attaching external VersaMax expansion modules through the dedicated expansion bus interface. Firmware flash compatibility across the expansion bus ensures synchronized data exchanges between the main CPU card and downstream I\/O modules, which preserves real-time control execution across field networks.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: How do field technicians configure communication protocols on the integrated RS-232 and RS-485 ports?\u003c\/p\u003e\n\u003cp\u003eA: Engineers set communication parameters, node addresses, and protocol assignments (SNP Slave or Modbus RTU Slave) using VersaMax programming software over the primary serial port connection.\u003c\/p\u003e\n\u003cp\u003eQ: What current limits apply to the integrated relay output channels?\u003c\/p\u003e\n\u003cp\u003eA: Each relay output contact supports a maximum continuous load of 2 A per point; exceeding this rating requires external interposing relays to prevent contact welding.\u003c\/p\u003e\n\u003cp\u003eQ: Does the unit support expansion I\/O modules while operating from the primary AC supply line?\u003c\/p\u003e\n\u003cp\u003eA: The internal power supply delivers logic power to the local processor and drives connected expansion modules up to the total backplane current limit of the expansion port.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cp\u003eFollow these sequential steps during physical installation and cabinet integration:\u003c\/p\u003e\n\u003col\u003e\n\u003cli\u003eMount the controller onto a standard 35 mm DIN rail or screw-fasten the housing directly to the enclosure backpanel using the mounting holes.\u003c\/li\u003e\n\u003cli\u003eDe-energize external supply lines before wiring the 120\/240 VAC main power terminals.\u003c\/li\u003e\n\u003cli\u003eRoute 24 VDC input signal cables separately from high-voltage AC output wires to prevent inductive noise coupling.\u003c\/li\u003e\n\u003cli\u003eConnect field cable shield drain wires directly to the cabinet ground bar via low-impedance copper conductors.\u003c\/li\u003e\n\u003cli\u003eApply operating power, monitor front panel LED status lights to confirm RUN state, and verify serial port link activity.\u003c\/li\u003e\n\u003c\/ol\u003e","brand":"GE Fanuc","offers":[{"title":"Default Title","offer_id":44521267953763,"sku":"IC200UDR005-BA","price":370.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0583\/5246\/8067\/files\/177._d0e4bc96-e501-45e8-8fc3-59b90ffbe943.jpg?v=1787815803","url":"https:\/\/www.autocontrolglobal.com\/products\/ge-fanuc-ic200udr005-ba-versamax-micro-plc-controller","provider":"AutoControl Global","version":"1.0","type":"link"}