GE Fanuc IC694MDL754-CO PACSystems RX3i Discrete Output Module
Manufacturer: GE Fanuc
-
Part Number: IC694MDL754-CO
Condition:New with Original Package
Product Type: Digital Output Modules
-
Country of Origin: USA
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
GE Fanuc IC694MDL754-CO PACSystems RX3i Discrete Output Module
Configured for high-speed discrete actuation in PACSystems RX3i controller networks, the GE Fanuc IC694MDL754-CO (IC694MDL754 Discrete Output Module) provides direct physical execution of binary voltage switching across field loads.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | IC694MDL754-CO |
| Brand | GE Fanuc |
| Origin | USA |
| Weight | 0.2 kg |
| Dimensions | 34 x 145 x 140 mm (1.5 x 5.5 x 5.5 in) |
| Operating Temp | 0 to 60 deg C (thermal derating above 42 deg C at 30 VDC) |
| Power Consumption | 300 mA maximum at 5 VDC (backplane bus) |
| Output Points | 32 sourcing (positive logic) points in 2 isolated groups of 16 |
| Operating Voltage Range | 10.2 to 30 VDC (12/24 VDC nominal) |
| Max Current per Point | 0.75 A (inrush 3.0 A for 10 ms) |
| Response Time | 0.5 ms maximum (turn-ON and turn-OFF) |
| Isolation | 250 VAC continuous (group-to-group and field-to-backplane) |
| Protection | Electronic Short Circuit Protection (ESCP) with auto-recovery |
Backplane Bus Communication Velocity and Firmware Compatibility
The IC694MDL754-CO converts internal CPU output commands into active sourcing currents, transferring state updates through high-speed backplane bus communication velocity architecture during every task execution cycle. Internal board logic maintains seamless firmware flash compatibility across RX3i processor revisions, allowing rapid updating of output status registers without interrupting adjacent I/O operations. The conformal coating applied across internal traces protects board components from humidity and airborne chemical contaminants while maintaining channel-to-logic galvanic isolation under continuous operation.
Frequently Asked Questions
Q: Does the IC694MDL754-CO module require external DC power to drive connected actuators?
A: Yes, each isolated group of 16 output channels requires an external field power supply supplying 10.2 to 30 VDC connected to the corresponding group power terminals on the terminal block.
Q: What happens when an output point on the IC694MDL754-CO experiences an overcurrent or short-circuit event?
A: Integrated Electronic Short Circuit Protection (ESCP) trips the affected output driver, illuminates the corresponding module fault indicator, and automatically resets the point once the overload condition clears and channel temperature normalizes.
Field Installation Guidelines
Verify that main power to the PACSystems RX3i backplane and all external field supply loops is switched off prior to installing or removing the IC694MDL754-CO. Slide the card into the target backplane slot until the rear edge connector seats fully into the rack header, then lock the retention latches securely. Attach either an IC694TBB032 or IC694TBS032 terminal block, wiring field loads using recommended gauge wire with signal cables separated from high-voltage AC conductors. Bond all shield wires to a single cabinet earth terminal to maintain surge immunity and prevent ground loop interference.