GE IC200ALG240-JE 16-Bit 8-Channel Analog Input Module
Manufacturer: GE Fanuc
-
Part Number: IC200ALG240-JE
Condition:New with Original Package
Product Type: Analog Input Modules
-
Country of Origin: USA
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
GE Fanuc IC200ALG240-JE VersaMax Analog Input Module
Configured for high-accuracy analog signal acquisition in GE Fanuc VersaMax PLC platforms, the GE Fanuc IC200ALG240-JE (IC200ALG240 Analog Input Module) provides direct physical signal processing across 8 input channels.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | IC200ALG240-JE |
| Brand | GE Fanuc |
| Origin | United States |
| Weight | 0.60 kg (1.31 lbs) |
| Dimensions | 120 mm x 90 mm x 50 mm |
| Operating Temp | 0 to +60 deg C |
| Power Consumption | 15 mA at 5 VDC (up to 80 mA max depending on baseplate configuration) |
| Number of Inputs | 8 channels |
| Input Signal Types | 4-20 mA / 0-10 VDC |
| Resolution | 16-bit |
| Isolation | Channel-to-channel / Field-to-logic isolation |
| Status Indicators | OK, Field Power LEDs |
Backplane Bus Communication Velocity & I/O Density Scaling
The module transfers digitized process variables directly to the VersaMax CPU across the internal carrier interface, using high-density I/O scaling to accommodate 8 analog measurement channels within a single chassis slot. Operating with an onboard backplane current draw as low as 15 mA at 5 VDC, the unit performs 16-bit A/D signal conversion while filtering common-mode power line noise through 50/60 Hz notch filters. Galvanic channel isolation prevents field ground loops from compromising backplane bus communication velocity or corrupting adjacent register values during continuous scan cycles.
Frequently Asked Questions
Q: How does the IC200ALG240-JE handle open-wire faults on transmitter loops?
A: The module executes internal open-wire detection logic for current-loop modes, immediately asserting diagnostic fault bits to the CPU controller when an open input loop is detected.
Q: Is external field power required to operate the channel inputs on this module?
A: Yes, field power must be supplied to the carrier terminal block to drive external sensor loops, and proper operation is indicated via the illuminated Field Power LED on the front faceplate.
Q: Can the IC200ALG240-JE be mounted on standard VersaMax carrier bases?
A: Yes, the module plugs directly into standard VersaMax snap-in I/O carriers, making electrical contact with the backplane bus and removable terminal strip without external ribbon cabling.
Field Installation Guidelines
Isolate all main power sources and field voltage supplies before installing or removing the module from its VersaMax carrier. Ensure the module is firmly aligned with the carrier guides and snapped into place to establish complete contact with the backplane connector. Run analog input wiring using twisted, shielded conductors, keeping signal lines separate from high-voltage AC cables. Connect the cable shields to the system ground bar at a single point to prevent ground potential loops from inducing signal noise.