GE IC200MDL750J 32-Point 12/24 VDC Output Module
GE IC200MDL750J 32-Point 12/24 VDC Output Module
GE IC200MDL750J 32-Point 12/24 VDC Output Module
/ 3

GE IC200MDL750J 32-Point 12/24 VDC Output Module

  • Manufacturer: GE Fanuc

  • Part Number: IC200MDL750J

  • Condition:New with Original Package

  • Product Type: Digital I/O Cards

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

GE Fanuc IC200MDL750J VersaMax Discrete Output Module

Configured for high-density discrete output control in GE Fanuc VersaMax PLC platforms, the GE Fanuc IC200MDL750J (IC200MDL750 Discrete Output Module) provides direct physical/electrical execution across 32 DC output points.

Hardware Specifications

Parameter Specification
Model IC200MDL750J
Brand GE Fanuc
Origin United States
Weight 0.31 kg (0.69 lbs)
Dimensions 120 mm x 90 mm x 50 mm
Operating Temp 0 to +60 deg C
Power Consumption 90 mA at 5 VDC (backplane draw)
Output Points 32 points (2 groups of 16 channels)
Output Voltage Range +10.2 to +30 VDC (12/24 VDC nominal)
Output Current 0.5 A per point (2.0 A max inrush for 100 ms)
Response Time ON: 0.2 ms, OFF: 1.0 ms
Isolation 1500 V RMS field to logic isolation
Status Indicators Individual channel green LEDs, OK LED, FLD PWR LED

Backplane Bus Communication Velocity & I/O Density Scaling

The module routes CPU control commands directly to external field loads through high-density I/O scaling, switching up to 32 discrete channels within a single VersaMax slot footprint. Operating with an internal backplane current draw of 90 mA at 5 VDC, the unit executes switching commands with a 0.2 ms ON-transition response time. Optical channel isolation rated at 1500 V RMS prevents field-side inductive spikes and load noise from interfering with backplane bus communication velocity or internal CPU logic states.

Frequently Asked Questions

Q: Does the IC200MDL750J support field-side short-circuit and overcurrent protection?

A: Yes, the module incorporates electronic short-circuit and overcurrent protection circuits to safeguard internal switching components against field wiring faults.

Q: How is the 32-point output capacity organized across the module field terminals?

A: The outputs are divided into 2 isolated groups containing 16 channels each, allowing separate power supply connections for different field load zones.

Q: Can the IC200MDL750J output module be hot-swapped during active CPU operation?

A: Field installation standards require isolating backplane rack power and external field voltage sources before removing or inserting the module on its carrier base.

Field Installation Guidelines

Ensure main backplane power and field 12/24 VDC load supplies are completely disconnected prior to installing or servicing the module. Align the housing side guides with the carrier base slot and press firmly until the locking mechanism fully snaps into place. Wire external load conductors to the removable terminal block, ensuring proper polarity for positive logic field devices. Connect the DIN rail or enclosure chassis ground to a primary earth bus bar to maintain effective surge protection limits and minimize signal noise.