{"product_id":"ge-is200tvibh2b-cc-mark-vi-speedtronic-vibration-input-board","title":"GE IS200TVIBH2B CC Mark VI Speedtronic Vibration Input Board","description":"\u003ch2\u003eGE IS200TVIBH2B CC Mark VI Vibration Input Terminal Board\u003c\/h2\u003e\n\u003cp\u003eThe \u003cstrong\u003eGE IS200TVIBH2B CC\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003eIS200TVIB\u003c\/strong\u003e Vibration Input Terminal Board, operates as a dedicated hardware component for dynamic sensor signal acquisition and conditioning within GE Mark VI Turbine Control platforms. The 6U board routes 8 vibration input channels connected to proximity probes and accelerometers across a +\/-24 VDC input range. Integrated analog signal conditioning, active filtering, and 1500 VDC channel-to-bus galvanic isolation process raw transducer signals before transmitting digitizing parameters across the control system backplane.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eIS200TVIBH2B CC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eGE\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.9 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e233 mm x 167 mm (Standard 6U VME Profile)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 deg C to +60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e+5 VDC via Backplane Bus\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eChannel Density\u003c\/td\u003e\n\u003ctd\u003e8 Vibration Input Channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTransducer Support\u003c\/td\u003e\n\u003ctd\u003eProximity Probes, Accelerometers\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSignal Input Range\u003c\/td\u003e\n\u003ctd\u003e+\/-24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation Voltage\u003c\/td\u003e\n\u003ctd\u003e1500 VDC Channel-to-Bus Isolation\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDiagnostics\u003c\/td\u003e\n\u003ctd\u003eChannel Health and Probe Status LED Indicators\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTermination\u003c\/td\u003e\n\u003ctd\u003eScrew Terminals with Wire Guards\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eBackplane Bus Communication Velocity and Deterministic Throughput\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eGE IS200TVIBH2B CC\u003c\/strong\u003e couples directly to the Mark VI system backplane bus to ensure rapid, deterministic delivery of vibration telemetry to central processor units. Analog-to-digital conversion circuits synchronize sampled channel data with controller execution frames, preventing latency accumulation in machinery protection loops. Integrated firmware compatibility maintains protocol integrity across backplane communication cycles, allowing real-time processing of high-frequency vibration signals without altering system bus bandwidth.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: How do integrated LED indicators assist during physical loop verification?\u003c\/p\u003e\n\u003cp\u003eA: Technicians use the front panel LEDs to observe active channel status, power rail health, and probe line integrity without interrupting signal acquisition.\u003c\/p\u003e\n\u003cp\u003eQ: What precautions prevent noise coupling on long proximity probe wire runs?\u003c\/p\u003e\n\u003cp\u003eA: Install shielded twisted-pair cabling, land shield drain wires at the dedicated cabinet earth point, and maintain physical separation from high-voltage AC conductors.\u003c\/p\u003e\n\u003cp\u003eQ: Can the terminal board handle inputs from different transducer types simultaneously?\u003c\/p\u003e\n\u003cp\u003eA: Yes, onboard conditioning circuits process inputs from both eddy-current proximity probes and piezoelectric accelerometers across individual channels within the +\/-24 VDC operational window.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cp\u003eFollow these core physical assembly and wiring practices during terminal board installation:\u003c\/p\u003e\n\u003col\u003e\n\u003cli\u003e\n\u003cstrong\u003eCarrier Board Mounting\u003c\/strong\u003e: Seat the 6U terminal board into the rack enclosure frame using standard mounting clips, verifying solid chassis contact to ground the assembly.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eField Cable Connection\u003c\/strong\u003e: Terminate field sensor leads into the screw terminals, ensuring the wire guards clamp conductors firmly without over-tightening.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eShield Earthing Discipline\u003c\/strong\u003e: Route cable drain wires directly to the designated earth bar, preserving a single-point ground connection to eliminate ground loop currents.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInterface Cable Attachment\u003c\/strong\u003e: Connect the multi-pin backplane interface ribbon cables to the board headers, locking side latches to prevent vibration-induced disconnects.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eTransducer Bias Check\u003c\/strong\u003e: Measure DC bias voltages at the field terminals prior to system startup to confirm proximity probes receive specified excitation power.\u003c\/li\u003e\n\u003c\/ol\u003e","brand":"GE Fanuc","offers":[{"title":"Default Title","offer_id":44451768467555,"sku":"IS200TVIBH2B CC","price":120.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0583\/5246\/8067\/files\/454._c897b748-0447-43f9-880a-5a6c38204dda.jpg?v=1786006042","url":"https:\/\/www.autocontrolglobal.com\/products\/ge-is200tvibh2b-cc-mark-vi-speedtronic-vibration-input-board","provider":"AutoControl Global","version":"1.0","type":"link"}