Hardy HI 1769-WS Weigh Scale Module for CompactLogix
Manufacturer: Allen-Bradley
-
Part Number: 1769-WS
Condition:New with Original Package
Product Type: Weigh Scale Module
-
Country of Origin: USA
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
Product Overview
The HI 1769-WS is a specialized, single-channel weigh scale module manufactured by Hardy Process Solutions for seamless integration into Allen-Bradley CompactLogix and MicroLogix 1500 systems. This module eliminates the need for standalone weight transmitters by providing a direct interface between strain-gauge load cells and the PLC backplane. Designed for high-precision industrial weighing, the HI 1769-WS features Hardy’s proprietary C2® electronic calibration and WAVERSAVER® technology, which filters out plant vibration to provide stable, accurate weight data. By processing weighing signals at the controller level, it reduces system latency and wiring complexity in high-speed batching and filling applications.
Detailed Technical Specifications
| Attribute | Details |
| Manufacturer | Hardy Process Solutions / Allen-Bradley |
| Model Number | HI 1769-WS |
| Product Type | Weigh Scale Interface Module |
| Platform Compatibility | CompactLogix, MicroLogix 1500 |
| Power Requirement | +5VDC (provided via backplane) |
| Backplane Current | < 0.5 Amps at 5V DC |
| Input Signal Range | -0.3mV through +15.3 mV |
| Excitation Voltage | 5V DC (Supports up to 8 350-ohm load cells) |
| Common Mode Rejection | 100dB at or below 60 Hz (minimum) |
| Resolution | 24-bit internal (1:8,388,608) |
| Conversion Rate | 100 updates per second |
| Calibration Methods | C2® Electronic Calibration and Traditional (test weights) |
| Vibration Rejection | WAVERSAVER® (0.25 Hz and above in 5 steps) |
| Operating Temp | 0 °C to +60 °C (32 °F to +140 °F) |
| Certifications | UL/cUL, CE, Class I Div 2 (Groups A, B, C, D) |