HIMax X-CPU 01 HIMA Central Processing Module Safety Logic Controller
Manufacturer: HIMA
-
Part Number: X-CPU 01
Condition:New with Original Package
Product Type: Central Processing Modules
-
Country of Origin: Germany
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
HIMA X-CPU 01 HIMax Central Processing Module
Configured for high-speed safety logic processing in HIMax Safety Instrumented Systems, the HIMA X-CPU 01 Processor Module (X-CPU 01) provides direct physical/electrical execution.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | X-CPU 01 |
| Brand | HIMA |
| Origin | Germany |
| Weight | 0.3 kg |
| Dimensions | 128 x 165 x 130 mm |
| Operating Temp | -20 deg C to +60 deg C |
| Power Consumption | ~15 W (Typical) |
| Supply Voltage | 24 VDC (+/-20%) |
| Processor Architecture | Multi-core CPU, 1.2 GHz |
| System Memory | 512 MB RAM, 256 MB Flash |
| Safety Response Time | <10 ms |
| Redundancy Switchover Time | <50 ms |
| Network Protocols | Ethernet (10/100/1000 Mbps), PROFIBUS, Modbus, CAN-Bus |
| Storage Temp | -40 deg C to +85 deg C |
| Relative Humidity | 5-95% non-condensing |
| Mounting Type | DIN-rail or modular slot installation |
Safety Instrumented Architecture & SIL 3 Execution
Engineered to fulfill IEC 61508 and IEC 61511 requirements up to SIL 3 certification, the X-CPU 01 processor employs triple modular redundancy (TMR) 2oo3 architecture concepts and hardware-level galvanic isolation to guarantee fail-safe state execution. Internal diagnostic monitoring continuously verifies logic parity across multi-core execution loops without increasing loop scan latencies. In redundant dual-processor configurations, the hardware logic controller executes automatic switchover routines within <50 ms upon detecting a processing anomaly, preserving uninterrupted safety signal processing across active backplane channels.
Frequently Asked Questions
Q: How does the X-CPU 01 maintain deterministic safety loop cycles under high communication network loads?
A: The multi-core processor segregates background communication handling (Ethernet, PROFIBUS, Modbus, CAN-Bus) from primary safety task processing, guaranteeing deterministic safety task execution with response times strictly under 10 ms.
Q: What operational restrictions apply when swapping an X-CPU 01 module in a redundant rack configuration?
A: Technicians can hot-swap a faulted primary or secondary CPU while the partner processor holds the safety loop. The newly inserted module automatically synchronized system memory (512 MB RAM) and flash runtime states within <50 ms without triggering an unexpected fail-safe state execution.
Field Installation Guidelines
Mount the processor module vertically in the designated HIMax rack slot or on a standard 35 mm DIN-rail inside an IP54 or better grounded metal cabinet. Ensure adequate clear space above and below the module heat sink fins to maintain passive convective airflow across the -20 deg C to +60 deg C operating thermal envelope. Connect the primary 24 VDC power leads using stranded copper conductors, keeping terminal torque within manufacturer specifications.
Grounding requires a dedicated low-impedance copper strap terminated directly from the rack frame to the main functional earth (FE) busbar. Route high-speed communication lines (Ethernet, PROFIBUS, CAN-Bus) through separate wire trays away from 230 VAC power feeders or inductive drive outputs. Always ensure shielded network cables terminate through standard metallic cable glands to guarantee continuous 360-degree shield contact against high-frequency industrial electromagnetic interference.