HIMax X-CPU 01 HIMA Central Processing Module Safety Logic Controller
HIMax X-CPU 01 HIMA Central Processing Module Safety Logic Controller
HIMax X-CPU 01 HIMA Central Processing Module Safety Logic Controller
/ 3

HIMax X-CPU 01 HIMA Central Processing Module Safety Logic Controller

  • Manufacturer: HIMA

  • Part Number: X-CPU 01

  • Condition:New with Original Package

  • Product Type: Central Processing Modules

  • Country of Origin: Germany

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

HIMA X-CPU 01 HIMax Central Processing Module

Configured for high-speed safety logic processing in HIMax Safety Instrumented Systems, the HIMA X-CPU 01 Processor Module (X-CPU 01) provides direct physical/electrical execution.

Hardware Specifications

Parameter Specification
Model X-CPU 01
Brand HIMA
Origin Germany
Weight 0.3 kg
Dimensions 128 x 165 x 130 mm
Operating Temp -20 deg C to +60 deg C
Power Consumption ~15 W (Typical)
Supply Voltage 24 VDC (+/-20%)
Processor Architecture Multi-core CPU, 1.2 GHz
System Memory 512 MB RAM, 256 MB Flash
Safety Response Time <10 ms
Redundancy Switchover Time <50 ms
Network Protocols Ethernet (10/100/1000 Mbps), PROFIBUS, Modbus, CAN-Bus
Storage Temp -40 deg C to +85 deg C
Relative Humidity 5-95% non-condensing
Mounting Type DIN-rail or modular slot installation

Safety Instrumented Architecture & SIL 3 Execution

Engineered to fulfill IEC 61508 and IEC 61511 requirements up to SIL 3 certification, the X-CPU 01 processor employs triple modular redundancy (TMR) 2oo3 architecture concepts and hardware-level galvanic isolation to guarantee fail-safe state execution. Internal diagnostic monitoring continuously verifies logic parity across multi-core execution loops without increasing loop scan latencies. In redundant dual-processor configurations, the hardware logic controller executes automatic switchover routines within <50 ms upon detecting a processing anomaly, preserving uninterrupted safety signal processing across active backplane channels.

Frequently Asked Questions

Q: How does the X-CPU 01 maintain deterministic safety loop cycles under high communication network loads?

A: The multi-core processor segregates background communication handling (Ethernet, PROFIBUS, Modbus, CAN-Bus) from primary safety task processing, guaranteeing deterministic safety task execution with response times strictly under 10 ms.

Q: What operational restrictions apply when swapping an X-CPU 01 module in a redundant rack configuration?

A: Technicians can hot-swap a faulted primary or secondary CPU while the partner processor holds the safety loop. The newly inserted module automatically synchronized system memory (512 MB RAM) and flash runtime states within <50 ms without triggering an unexpected fail-safe state execution.

Field Installation Guidelines

Mount the processor module vertically in the designated HIMax rack slot or on a standard 35 mm DIN-rail inside an IP54 or better grounded metal cabinet. Ensure adequate clear space above and below the module heat sink fins to maintain passive convective airflow across the -20 deg C to +60 deg C operating thermal envelope. Connect the primary 24 VDC power leads using stranded copper conductors, keeping terminal torque within manufacturer specifications.

Grounding requires a dedicated low-impedance copper strap terminated directly from the rack frame to the main functional earth (FE) busbar. Route high-speed communication lines (Ethernet, PROFIBUS, CAN-Bus) through separate wire trays away from 230 VAC power feeders or inductive drive outputs. Always ensure shielded network cables terminate through standard metallic cable glands to guarantee continuous 360-degree shield contact against high-frequency industrial electromagnetic interference.