Honeywell 900G01-0202 HC900 Series Digital Input Modules
Honeywell 900G01-0202 HC900 Series Digital Input Modules
Honeywell 900G01-0202 HC900 Series Digital Input Modules
/ 3

Honeywell 900G01-0202 HC900 Series Digital Input Modules

  • Manufacturer: Honeywell

  • Part Number: 900G01-0202

  • Condition:New with Original Package

  • Product Type: Digital Input Modules

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Honeywell 900G01-0202 HC900 Series 16-Channel DI Module

The Honeywell 900G01-0202, also cataloged as the 900G01 Digital Input Module, operates as a dedicated hardware component for discrete signal acquisition within Honeywell HC900 and ControlEdge HC900 controller platforms. The module interfaces with field switches, relays, and binary sensors, processing raw 24 VDC electrical input transitions into logic states and routing them across the system backplane for immediate controller execution.

Hardware Specifications

Parameter Specification
Model 900G01-0202
Brand Honeywell
Origin USA
Weight 0.175 kg
Dimensions 137 x 35.6 x 137.16 mm
Operating Temp 0 to +60 deg C
Storage Temp -40 to +85 deg C
Power Consumption 130 mA maximum at 5 VDC, 40 mA maximum at 24 VDC
Number of Channels 16 channels (single-ended)
Nominal Input Voltage 24 VDC
Controller Supply Voltage 15 VDC nominal
Input Current Range 3-8 mA per channel
Switching Current 2.6 mA nominal
Maximum Contact Resistance 1000 ohms
OFF to ON Response Time 4 ms maximum
ON to OFF Response Time 6 ms maximum
Isolation Galvanic isolation between field wiring and internal module/backplane circuitry
Humidity Range 5% - 95% non-condensing
Certifications CE

Galvanic Isolation and Signal Integrity

The module utilizes optical and galvanic isolation elements between the field-side wiring terminals and the internal system backplane logic. This architectural barrier prevents voltage surges, ground loop currents, and electrical noise transient phenomena from disrupting the core processor operations. By isolating the 16 single-ended input channels from the primary logic bus, the assembly maintains signal loop fidelity and prevents localized field wiring faults from propagating into adjacent hardware slots.

Frequently Asked Questions

Q: What are the backplane power supply current demands for this module? A: The hardware draws a maximum current of 130 mA from the 5 VDC backplane logic rail and a maximum of 40 mA from the 24 VDC power rail during active operations.

Q: How do the input response times affect high-speed signal capture? A: The digital filter and signal conditioning circuits introduce a maximum propagation delay of 4 ms during an OFF-to-ON transition and a maximum of 6 ms during an ON-to-OFF transition.

Q: What is the maximum allowable loop resistance for connected field contacts? A: The input conditioning circuitry requires that external field switches or relay contacts maintain a maximum contact resistance below 1000 ohms to guarantee reliable logic state transitions.

Field Installation Guidelines

  1. Enclosure Grounding: Establish a low-impedance connection between the chassis mounting rail and the master instrument ground bus to ensure the galvanic isolation barriers perform within rated surge limits.
  2. Wiring Routing Constraints: Maintain physical separation between the 24 VDC input signal loops and any high-voltage AC power distribution conductors within the panel layout to minimize capacitive cross-talk.
  3. Module Insertion: Verify that the controller rack alignment guides are clear of debris before seating the module into the backplane connectors to prevent mechanical stress or pins misalignment.