Honeywell CC-TAID01 Series C DI DO Module
Manufacturer: HONEYWELL
-
Part Number: CC-TAIDO1
Condition:New with Original Package
Product Type: Digital I/O Cards
-
Country of Origin: Sweden
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
aHoneywell CC-TAID01 Series C Module
Configured for discrete field monitoring and actuation in Experion PKS Series C networks, the Honeywell CC-TAID01 (CC-TAID01 Digital Input/Output Module) provides direct physical/electrical execution. It serves as the primary hardware interface translating state changes from proximity switches, pushbuttons, and interlocks into system logic variables, while simultaneously driving solid-state control signals to remote relays and contactor coils.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | CC-TAID01 |
| Brand | Honeywell |
| Part Number | 51306733-175 REV B |
| Origin | USA |
| Weight | 0.5 kg |
| Dimensions | 267 x 178 x 51 mm |
| Operating Temp | -20 to +55 deg C |
| Power Consumption | 60 W |
| Product Type | Digital Input/Output Module (DI/DO) |
| Number of Channels | 32 (configurable) |
| Signal Types Supported | 24 VDC logic signals |
| Input Characteristics | Dry contact or voltage input, optically isolated |
| Output Characteristics | Solid-state transistor outputs, 24 VDC |
| Isolation | Channel-to-channel and channel-to-system |
| Operating Voltage | Powered via Series C chassis backplane |
Process Control & DCS Instrumentation Matrix
The Honeywell CC-TAID01 houses a 32-channel discrete matrix where each point accepts software allocation as either a digital input or digital output loop. The digital input paths apply optical isolation circuits to suppress field-induced transients, processing both voltage-driven loops and dry contact topologies operating at nominal 24 VDC levels. The digital output paths leverage solid-state transistor switching components to control independent 24 VDC actuation lines. Channel-to-channel and channel-to-system isolation networks isolate the central backplane bus from external electromagnetic disturbances. Local diagnostic subroutines continuously evaluate module status, reporting fault detection alerts and updating physical LED indicators mounted on the front face assembly.
Frequently Asked Questions
Q: How is the input logic state determined when using dry contact field devices?
A: The module supplies an internal wetting voltage to detect contact transition states, utilizing the onboard optical isolators to capture the circuit opening or closing while keeping the central backplane electrically separated from the field loop.
Q: Can channels be reconfigured dynamically during active system execution?
A: Channel direction parameters (input or output) must be defined and compiled within the Experion builder environment; changing the functional configuration of a point requires downloading the modified block assignment to the controller node.
Field Installation Guidelines
- Insert the module into the designated Series C slot until the card edge connectors fully engage with the passive backplane, securing the retention fasteners to maintain electrical contact under high-vibration conditions.
- Route all 24 VDC discrete wiring away from high-power AC motor leads and variable frequency drive cables to eliminate inductive noise coupling on the input sensing channels.
- Ensure all external power supplies providing auxiliary 24 VDC current for output loads share a common reference ground terminal bar inside the local marshaling cabinet to prevent voltage reference drift.