Honeywell TC-IXR061 6-Channel RTD Input Module | 16-Bit
Honeywell TC-IXR061 6-Channel RTD Input Module | 16-Bit
Honeywell TC-IXR061 6-Channel RTD Input Module | 16-Bit
/ 3

Honeywell TC-IXR061 6-Channel RTD Input Module | 16-Bit

  • Manufacturer: Honeywell

  • Part Number: TC-IXR061

  • Condition:New with Original Package

  • Product Type: Analog Input Module

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Honeywell TC-IXR061 Experion PKS Isolated 6-Channel RTD Input Module

Product Description

The TC-IXR061 (TC-IXR061) is a high-performance, galvanically isolated analog input module specifically engineered for the Honeywell Experion PKS, C300, and LS control systems. Designed for precision temperature acquisition, the TC-IXR061 (TC-IXR061) features six independent channels, each providing dedicated isolation to ensure signal integrity in electrically noisy industrial environments.

Unlike standard high-density modules, the TC-IXR061 (TC-IXR061) focuses on high-fidelity resistance measurement, supporting a vast library of Platinum, Nickel, and Copper RTD sensors. With a rapid 50-millisecond update rate across all channels and integrated open-wire detection, it provides process engineers with the deterministic data needed for critical thermal control loops in power plants, chemical refineries, and pharmaceutical manufacturing facilities.

Detailed Technical Specifications

The following technical parameters outline the hardware capabilities and environmental tolerances of the TC-IXR061:

  • Manufacturer: Honeywell

  • Model Number: TC-IXR061

  • Product Type: Isolated RTD Input Module

  • System Compatibility: Experion PKS, C300, TPS Evolution, Experion LS

  • Number of Channels: 6 Galvanically Isolated Channels

  • A/D Resolution: 16-bit per channel

  • Signal Input Ranges: 1–487 Ω, 2–1000 Ω, 4–2000 Ω, 8–4020 Ω

  • Accuracy: ±0.1% Full Scale at 25°C

  • Update Rate: 50 milliseconds for all channels

  • Channel Bandwidth: DC to 15 Hz (-3 dB)

  • Isolation: Channel-to-bus and channel-to-channel galvanic isolation

  • Common Mode Rejection: 120 dB @ 60 Hz; 100 dB @ 50 Hz

  • Open Wire Detection: Reported in < 5 seconds

  • Temperature Drift: Input Offset: 10 mΩ/°C; Gain Drift: 50 ppm/°C

  • Connection Interface: 20-position terminal block (TC_TBNH)

  • Power Dissipation: Maximum 4.3 W

  • Operating Temperature: -20 °C to +55 °C

  • Weight: 0.62 lbs (0.28 kg)