GE IC200CHS014G VersaMax Thermocouple Compensation Terminal Block
The GE IC200CHS014G, also cataloged as the IC200CHS014 Thermocouple Compensation Interposing I/O Terminal Block, operates as a dedicated hardware component for cold junction compensation and physical signal routing within VersaMax I/O system networks.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | IC200CHS014G |
| Brand | GE Fanuc / Emerson |
| Origin | USA |
| Weight | 0.23 kg (0.51 lbs) |
| Dimensions | 110 mm W x 50 mm D x 66.8 mm H |
| Operating Temp | -40 to 60 deg C |
| Storage Temp | -40 to 85 deg C |
| Power Consumption | Passive (Powered via backplane/module interface) |
| Terminal Count | 36 box-style screw terminals |
| Single Wire Size | 0.36 to 2.1 mm2 |
| Dual Wire Size | Up to 0.86 mm2 |
| Operating Altitude | Up to 1000 m |
| Relative Humidity | 5 to 95% (non-condensing) |
| Voltage Isolation | 250 VAC continuous, 1500 VAC for 1 minute |
| Status Indicator | Module OK LED |
| Mounting | Standard 35 mm DIN rail or panel mounting |
| Compliance | CE, UL, CSA certified |
Backplane Bus Communication and Network Architecture
The IC200CHS014G carrier interfaces field thermocouple sensors directly with VersaMax analog input hardware, maintaining high backplane bus communication velocity across the I/O rack rail. Internal cold junction compensation (CJC) thermistors stabilize millivolt voltage translation before transferring telemetry data across the local bus structure. Hardware design guidelines ensure complete firmware flash compatibility with base CPUs, while expanding structural I/O density scaling options across process interface banks.
Frequently Asked Questions
Q: Does the IC200CHS014G terminal block provide internal signal processing or active digital outputs?
A: No, this unit functions strictly as a passive physical interposing carrier and cold-junction compensation interface. It must be paired with an active VersaMax analog I/O module to process field signal data.
Q: What are the wire gauge and clamping limits for the 36 terminal connections?
A: The box-style terminals accommodate single conductors from 0.36 to 2.1 mm2, or dual conductors up to 0.86 mm2 per terminal point.
Field Installation Guidelines
Mount the interposing block onto a standard 35 mm DIN rail or secure it to a backpanel using mounting screws. Strip field thermocouple wiring to recommended lengths before inserting into the 36 box-style terminals, tightening screw clamps to standard torque limits. Keep low-voltage thermocouple leads separate from high-voltage power conduits to limit EMI cross-coupling. Connect cable shielding to the dedicated cabinet ground point to preserve cold-junction measurement accuracy.