IC200EBI001-PL GE Fanuc VersaMax Ethernet Network Module
IC200EBI001-PL GE Fanuc VersaMax Ethernet Network Module
IC200EBI001-PL GE Fanuc VersaMax Ethernet Network Module
/ 3

IC200EBI001-PL GE Fanuc VersaMax Ethernet Network Module

  • Manufacturer: GE Fanuc

  • Part Number: IC200EBI001-PL

  • Condition:New with Original Package

  • Product Type: Network Interface Modules

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

GE Fanuc IC200EBI001-PL VersaMax Ethernet Network Interface Module

Configured for industrial Ethernet network bridge execution in VersaMax PLC systems, the GE Fanuc IC200EBI001-PL (IC200EBI001 Ethernet Network Interface Module) provides direct physical/electrical execution for real-time I/O telemetry exchange across local control nodes.

Hardware Specifications

Parameter Specification
Model IC200EBI001-PL
Brand GE Fanuc
Origin USA
Weight 0.14 kg (0.31 lbs)
Dimensions 133.4 mm x 69.1 mm x 85.9 mm
Operating Temp 0 deg C to +60 deg C
Power Consumption 175 mA at +5 VDC, 425 mA at +3.3 VDC
Interface Type Ethernet RJ-45 (10Base-T / 100Base-TX auto-negotiation)
Network Protocols TCP/IP, UDP
I/O Capacity 1024 bytes total (512 bytes input / 512 bytes output)
Module Expansion Up to 64 I/O modules across 7 expansion racks (Release 1.01+)
Mounting Standard DIN-rail mounting

Backplane Bus Communication & EtherNet/IP Deterministic Networks

The network interface maps local and remote I/O data arrays across Ethernet networks with minimal network transport latency, processing TCP/IP and UDP packet streams simultaneously. Integrated logic circuits manage backplane bus communication velocity across up to 7 expansion racks, maintaining cyclic update speeds without dropping I/O image tables. Furthermore, internal flash memory supports firmware flash compatibility with main VersaMax CPU modules, ensuring continuous diagnostic monitoring, status LED reporting, and uninterrupted backplane communication under high data throughput conditions.

Frequently Asked Questions

Q: How does the IC200EBI001-PL handle I/O rack expansion across local backplane networks?

A: Starting with firmware Release 1.01 or later, the interface module orchestrates process data transfer for up to 64 I/O modules distributed across 7 expansion racks, mapping 512 input bytes and 512 output bytes directly to the host CPU memory table.

Q: What power rails must the backplane supply to keep the module operational?

A: The backplane power supply must deliver a regulated +5 VDC rail drawing up to 175 mA alongside a +3.3 VDC logic rail drawing up to 425 mA to maintain proper Ethernet transceiver operation.

Field Installation Guidelines

Mount the network interface module securely onto a standard 35 mm DIN rail inside an enclosure that maintains ambient operating temperatures between 0 deg C and +60 deg C. Connect Category 5e or higher shielded Ethernet cabling through the RJ-45 connector, keeping network cables physically separated from three-phase AC power wiring and variable frequency drive leads to prevent electromagnetic noise. Field technicians should ground the DIN rail to a central panel earthing bar with a low-impedance copper strap, verify that backplane bus connectors align before snapping expansion racks together, and confirm supply voltage stability before applying system power.

You may also like