{"product_id":"ic200mdd845-ge-versamax-16-input-8-relay-output-module","title":"IC200MDD845 GE VersaMax 16 Input 8 Relay Output Module","description":"\u003ch2\u003eGE Fanuc IC200MDD845 VersaMax Mixed Discrete I\/O Module\u003c\/h2\u003e\n\u003cp\u003eConfigured for discrete signal acquisition and high-power relay switching in VersaMax I\/O backplane racks, the \u003cstrong\u003eGE Fanuc IC200MDD845\u003c\/strong\u003e (\u003cstrong\u003eIC200MDD845\u003c\/strong\u003e Mixed Discrete I\/O Module) provides direct physical\/electrical execution. The module integrates 16 digital inputs operating at 24 VDC positive logic along with 8 Form A relay outputs across a single backplane slot. Field-side logic signals and output contact circuits maintain 1500 V galvanic isolation from internal backplane logic circuitry.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eIC200MDD845\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eGE Fanuc\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.159 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e133.4 x 85.9 x 69.1 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 deg C to +60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e270 mA at 5 VDC (backplane draw)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Channels\u003c\/td\u003e\n\u003ctd\u003e16 discrete inputs (24 VDC nominal, positive logic)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Current\u003c\/td\u003e\n\u003ctd\u003e2.0 to 5.5 mA ON, 0 to 0.5 mA OFF\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Channels\u003c\/td\u003e\n\u003ctd\u003e8 relay outputs (Form A)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Current Rating\u003c\/td\u003e\n\u003ctd\u003e2.0 A resistive per point\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Voltage Ranges\u003c\/td\u003e\n\u003ctd\u003e5-30 VDC (2.0 A), 31-125 VDC (0.2 A), 5-265 VAC (2.0 A)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCircuit Isolation\u003c\/td\u003e\n\u003ctd\u003e1500 V field-to-logic isolation\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStatus Indicators\u003c\/td\u003e\n\u003ctd\u003eIndividual channel status LEDs, Module OK LED\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting Options\u003c\/td\u003e\n\u003ctd\u003eDIN-rail or direct panel mounting\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eBackplane Communication and I\/O Density Scaling\u003c\/h3\u003e\n\u003cp\u003eThe module communicates via the VersaMax parallel backplane bus architecture, maintaining continuous input scanning and output latch updates without degrading bus transfer speed. High I\/O density scaling allows mixed discrete signal processing in a single module footprint, reducing backplane carrier slot requirements. Additionally, onboard microcode maintains firmware flash compatibility with VersaMax CPUs, ensuring deterministic signal propagation times across multi-module expansion racks.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: What is the backplane current draw requirement for the IC200MDD845 module?\u003c\/p\u003e\n\u003cp\u003eA: The module draws 270 mA at 5 VDC directly from the VersaMax backplane carrier power rail during normal operational states.\u003c\/p\u003e\n\u003cp\u003eQ: Are the Form A relay output channels individually isolated from one another?\u003c\/p\u003e\n\u003cp\u003eA: Yes, each of the 8 relay output channels provides individual isolation, allowing independent switching across distinct AC and DC voltage potential groups.\u003c\/p\u003e\n\u003cp\u003eQ: Does the IC200MDD845 support hot-swapping under powered rack conditions?\u003c\/p\u003e\n\u003cp\u003eA: Module removal or insertion requires backplane power to be deactivated unless installed on a VersaMax hot-insert carrier designed specifically for field module replacement.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cp\u003eSnap the IC200MDD845 module firmly onto its corresponding VersaMax carrier unit mounted on a standard 35 mm DIN rail or panel baseplate. Verify that the module locking mechanism fully engages with the carrier housing before applying power to the backplane.\u003c\/p\u003e\n\u003cp\u003eRoute all 24 VDC field input conductors and AC\/DC output contact wiring through separate wire trays to prevent cross-talk coupling between high-voltage power loads and low-voltage DC logic signals. Maintain a minimum separation distance of 200 mm between AC load conductors and low-voltage sensor cabling. Ensure field power wiring connected to the relay terminals utilizes inductive load suppression devices (such as RC snubbers across AC coils or flyback diodes across DC coils) to suppress voltage transients during relay contact interruption.\u003c\/p\u003e","brand":"GE Fanuc","offers":[{"title":"Default Title","offer_id":43876858691683,"sku":"IC200MDD845","price":120.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0583\/5246\/8067\/files\/237_c32a26bb-463f-4f6c-a738-4e96dde1572b.jpg?v=1765180044","url":"https:\/\/www.autocontrolglobal.com\/products\/ic200mdd845-ge-versamax-16-input-8-relay-output-module","provider":"AutoControl Global","version":"1.0","type":"link"}