IC200UEI016 GE Fanuc VersaMax Micro Discrete Input Module
IC200UEI016 GE Fanuc VersaMax Micro Discrete Input Module
IC200UEI016 GE Fanuc VersaMax Micro Discrete Input Module
/ 3

IC200UEI016 GE Fanuc VersaMax Micro Discrete Input Module

  • Manufacturer: GE Fanuc

  • Part Number: IC200UEI016

  • Condition:New with Original Package

  • Product Type: Digital Input Modules

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

GE IC200UEI016 VersaMax Micro Discrete Input Expansion Module

Configured for discrete digital signal acquisition in VersaMax Micro automation platforms, the GE IC200UEI016 (IC200UEI016-A Discrete Expansion Module) provides direct physical/electrical execution. The unit accepts 24 VDC positive logic signals from field devices such as limit switches, pushbuttons, and proximity sensors, translating electrical state changes across 16 channels into digital data for the local controller.

Hardware Specifications

Parameter Specification
Model IC200UEI016
Brand GE Fanuc / Emerson
Origin USA
Weight 0.91 kg (2.00 lbs)
Dimensions 150 mm W x 76 mm D x 90 mm H
Operating Temp 0 to 60 deg C
Power Consumption 4 W
Input Points 16 discrete DC inputs
Input Voltage Range 0 to 30 VDC (24 VDC nominal)
Input Logic Type Positive logic (ON >= 15 VDC, OFF <= 5 VDC)
Input Current 7 mA per point at 24 VDC
Input Response Time 1 ms typical
Isolation 1500 V RMS field-to-logic, 500 V RMS between groups
Status Indicators 16 channel LEDs, 1 module OK LED
Sensor Power Output 200 mA at 24 VDC
Expansion Limit Maximum 4 expansion modules per Micro PLC base unit

Backplane Bus Communication and Network Architecture

The IC200UEI016 interfacing circuit interfaces directly with the VersaMax Micro backplane bus to ensure backplane bus communication velocity stays synchronized with central CPU scan cycles. Firmware flash compatibility within the main controller manages channel mapping without extra programming steps. The unit scales I/O density by accommodating up to 4 expansion modules per base controller, sustaining 1 ms signal processing speed while maintaining channel isolation integrity across the local expansion rail.

Frequently Asked Questions

Q: How does the module handle signal isolation between field wiring and logic circuits?

A: Optical isolation circuitry limits transient voltage transfers by providing 1500 V RMS field-to-logic isolation and 500 V RMS isolation between internal channel groups.

Q: What are the electrical threshold limits for switching a channel between ON and OFF states?

A: An input point registers an ON state at or above 15 VDC and transitions to an OFF state at or below 5 VDC, drawing approximately 7 mA per channel at nominal 24 VDC.

Field Installation Guidelines

Mount the unit on standard 35 mm DIN rail or attach directly to a mounting panel with screws. Secure the expansion bus cable to the base controller before applying power. Route field input wiring away from high-voltage AC lines to minimize noise induction, ensuring external 24 VDC power connects with correct polarity to support the positive logic configuration. Ground the panel assembly to a low-impedance copper busbar, and verify total current draw does not exceed the 200 mA limit when utilizing onboard sensor power.