IC660BBD120 GE Fanuc Genius I/O High-Speed Counter Block
Manufacturer: GE Fanuc
-
Part Number: IC660BBD120
Condition:New with Original Package
Product Type: High-Speed Counter Blocks
-
Country of Origin: USA
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
GE IC660BBD120 Genius I/O High-Speed Counter Block
Configured for high-speed pulse acquisition and real-time frequency counting in Genius I/O serial networks, the GE IC660BBD120 (IC660BBD120 High-Speed Counter Block) provides direct physical/electrical execution.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | IC660BBD120 |
| Brand | GE Fanuc |
| Origin | USA |
| Weight | 4.00 lbs (1.81 kg) |
| Dimensions | 8.83 x 3.34 x 3.91 inches (22.44 x 8.48 x 9.93 cm) |
| Operating Temp | 0 to 60 deg C |
| Power Consumption | 8 W |
| Operating Voltage Range | 18-56 VDC (24/48 VDC nominal) |
| Number of Counters | 1, 2, or 4 configurable counters |
| Discrete Inputs | 12 inputs (5 to 30 VDC) |
| Maximum Input Frequency | 200 kHz (high-frequency filter selected) |
| Discrete Outputs | 4 outputs |
| Additional Outputs | 1 oscillator output, 1 rated 5 VDC output (4.75 to 5.25 VDC) |
| Minimum Pulse Width | 2.5 us (high-frequency), 12.5 ms (low-frequency) |
| Input Response Time | 0.5 ms (plus filter delay) |
| Electrical Isolation | 1500 V block-to-block isolation |
| Bus Interface | Genius RS-485 serial bus |
| Status Indicators | LEDs for Unit OK and I/O Enabled status |
Deterministic Network Backplane Communication
The IC660BBD120 processes pulse train accumulation independently of host controller PLC scan cycles, executing high-speed counting up to 200 kHz. Built-in digital filtering defaults to a 2.5 us high-frequency threshold for fast encoder signals or a 12.5 ms low-frequency threshold for 40 Hz maximum mechanical contact debouncing. Serial bus data transfers execute deterministically via the Genius RS-485 bus protocol, transmitting accumulated register counts to host Series 90-30 and 90-70 CPUs while maintaining 1500 V galvanic block isolation to preserve signal integrity against common-mode electrical transients.
Frequently Asked Questions
Q: Which base components assemble together to form the complete high-speed counter block assembly?
A: The complete block assembly consists of the electronic module base cataloged as IC660EBD120 mated to the field wiring terminal assembly cataloged as IC660TBD120.
Q: How does switching between high-frequency and low-frequency input filtering change counting performance?
A: Selecting the high-frequency filter sets a 2.5 us minimum input pulse width capable of tracking inputs up to 200 kHz. Selecting the low-frequency filter sets a 12.5 ms minimum pulse width capped at a maximum count rate of 40 Hz to filter out contact chatter.
Field Installation Guidelines
Mount the IC660BBD120 vertically on a panel or DIN rail inside an industrial enclosure, keeping a minimum of 2 inches of free vertical space for thermal heat dissipation. Direct field wiring to the IC660TBD120 terminal assembly, keeping 5-30 VDC encoder and pulse lines segregated from AC power carrying lines. Ground the Genius RS-485 serial communication shield wire at a single point to prevent ground loops across distributed network drops.