IC693ALG223 GE Series 90-30 16-Channel Analog Input Module
Manufacturer: GE Fanuc
-
Part Number: IC693ALG223
Condition:New with Original Package
Product Type: Analog Input Modules
-
Country of Origin: USA
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
GE IC693ALG223 Series 90-30 Analog Input Module
Configured for high-density signal acquisition in Series 90-30 PLC platforms, the GE IC693ALG223 (IC693ALG223 Analog Input Module) provides direct physical and electrical execution of 16-channel analog-to-digital conversion for process variable monitoring.
Suffix Breakdown & Model Matrix
The IC693ALG223 identifier follows the GE Fanuc standardized nomenclature for Series 90-30 I/O modules. The "ALG" prefix designates the analog product line, while the "223" code denotes the specific channel density (16 channels) and signal range capabilities. Minor revision suffixes occasionally appear on the module faceplate to denote PCB fabrication batches or compliance updates, though the functional electrical specifications remain consistent across the standard hardware lifecycle.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | IC693ALG223 |
| Brand | GE Fanuc Series 90-30 |
| Origin | USA |
| Weight | 0.48 kg |
| Dimensions | 5.0 in x 7.0 in (12.7 cm x 17.8 cm) |
| Operating Temp | 0 deg C to 60 deg C |
| Power Consumption | 120 mA at 5 VDC, 65 mA at 24 VDC |
| Performance | 16 channels, 12-bit resolution, 13 ms update rate |
PLC Backplane Integration and Deterministic Communication
The IC693ALG223 interfaces with the Series 90-30 backplane to transmit converted digital values to the CPU module. The architecture utilizes a high-speed bus communication velocity, ensuring that all 16 channels are refreshed every 13 ms, providing the deterministic data throughput required for process control loops. The module firmware supports flash-based configuration settings, allowing the user to map input ranges via the programming software. Galvanic isolation at 1500 V RMS protects the logic backplane from transient spikes on the field-side sensor wiring, maintaining data integrity even in environments with high electromagnetic interference.
Frequently Asked Questions
Q: Does the IC693ALG223 support hot-swapping into the Series 90-30 rack?
A: No, the module does not support true hot-swapping. The PLC rack power must be cycled or disconnected before removing or inserting the module to prevent electrical damage to the backplane connectors.
Q: Is external power required for the module to function?
A: Yes, the module requires a user-supplied 24 VDC source, consuming 65 mA for the analog circuitry, in addition to the 5 VDC power drawn from the PLC backplane for logic operations.
Field Installation Guidelines
When installing the IC693ALG223, ensure the Series 90-30 rack is de-energized. Seat the module firmly into the designated slot, ensuring the backplane pins are fully engaged before tightening the module securing screws. Terminate field wiring using the removable terminal block, ensuring that cable shields are properly tied to the system ground bus to mitigate common-mode noise. For current loop inputs, verify that the load resistors are properly matched to the signal source to maintain the accuracy of the 4-20 mA readings. Prior to placing the module into production, perform a channel-by-channel calibration check using a precision signal source.