IC697ALG230J GE Series 90-70 Analog Input Module
IC697ALG230J GE Series 90-70 Analog Input Module
IC697ALG230J GE Series 90-70 Analog Input Module
/ 3

IC697ALG230J GE Series 90-70 Analog Input Module

  • Manufacturer: GE Fanuc

  • Part Number: IC697ALG230J

  • Condition:New with Original Package

  • Product Type: Analog Input Module

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

GE IC697ALG230J Series 90-70 Analog Input Module

Configured for analog signal processing in Series 90-70 PLC platforms, the GE IC697ALG230J (IC697ALG230 Analog Input Module) provides direct physical/electrical execution.

Suffix Breakdown & Model Matrix

The IC697ALG230 platform utilizes specific revision suffixes to identify hardware iterations, channel density parameters, and diagnostic profiles across single-slot VME form factors.

Catalog Model Revision Suffix Input Channels Configured Signal Types Resolution
IC697ALG230 Base Model 8 differential +/-10 VDC, 4-20 mA 16-bit
IC697ALG230J J Revision 16 single-ended +/-10 VDC, 0-10 VDC, +/-5 VDC, 0-5 VDC, 1-5 VDC, 4-20 mA, 0-20 mA 12-bit

Hardware Specifications

Parameter Specification
Model IC697ALG230J
Brand GE
Origin USA
Weight 0.82 kg (1.81 lbs)
Dimensions Standard Series 90-70 single-slot module
Operating Temp 0 to 60 deg C (32 to 140 deg F)
Power Consumption 1.2 A at +5 VDC backplane power
Input Channels 16 single-ended (or 8 differential base configuration)
Resolution 12-bit (4096 counts)
Input Impedance Voltage: >100 kOhm; Current: 250 Ohm
Accuracy +/-0.25% of full scale
Isolation 1500 V field-to-logic galvanic protection
Terminal Connector 40-pin terminal block

Backplane Bus & Deterministic Networks

The module interfaces with the Series 90-70 rack through high-speed VMEbus connections, providing real-time data transfer across internal register tables. High backplane bus communication velocity allows uninterrupted scan execution, while proper firmware flash compatibility ensures synchronized multi-channel sampling. The module scales system I/O density by converting multiple field process variables simultaneously and transferring digitized register counts directly to the CPU logic engine.

Frequently Asked Questions

Q: Can the IC697ALG230J module be replaced while the Series 90-70 PLC rack remains powered?

A: No, this hardware does not support hot-swapping. You must completely switch off main rack power prior to module insertion or removal to prevent damage to backplane logic circuits.

Q: How does the module handle signal noise on current loops?

A: The module relies on 1500 V field-to-logic isolation and onboard filtering. External twisted-pair shielded cable, grounded properly at a single grounding bus, prevents signal noise from corrupting digitized input counts.

Field Installation Guidelines

Mount the IC697ALG230J securely into a dedicated Series 90-70 VME rack slot with system power turned off. Tighten top and bottom retaining screws to ensure proper frame ground contact. Route all field wiring through the 40-pin terminal block, keeping low-voltage analog cables physically separated from high-voltage AC lines. Connect signal wiring shields to a single earth ground point at the panel enclosure to eliminate ground loops and maintain the 1500 V galvanic isolation threshold.

You may also like