  • Manufacturer: GE Fanuc

  • Part Number: KJ3221X1 -EA1

  • Condition:New with Original Package

  • Product Type: Analog Output Modules

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Emerson KJ3221X1-BA1 DeltaV Series

The Emerson KJ3221X1-BA1, also cataloged as the KJ3221X1-BA1 AO 8-Channel 4-20 mA HART Series 2 Redundant Card, operates as a dedicated hardware component for 8-channel analog current loop output execution within DeltaV LocalBus instrumentation networks.

Hardware Specifications

Parameter Specification
Model KJ3221X1-BA1 (Alternate Part No: 12P2531X022, 12P2531X112, 12P2531X052, 12P2531X062, 12P2531X082, 12P2531X102)
Brand Emerson (DeltaV)
Origin USA
Weight 0.23 kg (0.51 lbs) net / 1.50 kg shipping footprint
Dimensions Standard DeltaV Series 2 card dimensions
Operating Temp -40 to +70 deg C
Power Consumption LocalBus: 12 VDC at 150 mA / Bussed Field Power: 24 VDC at 300 mA
Channel Count 8 analog output channels
Signal Range 4-20 mA
Digital Protocol Integrated HART pass-through communication
Field Circuit Rating 24 VDC at 23 mA
Mechanical Keying Terminal block key position A4
Protection Class IP20
Relative Humidity 5% to 95%, non-condensing
Mechanical Shock 10 g, half-sine for 11 ms
Mechanical Vibration 1 mm peak-to-peak from 5 to 16 Hz; 0.5 g from 16 to 150 Hz
Airborne Contaminants ISA-S71.04-1985 Class G3 compliance

4-20 mA HART Loop Protocol and Channel-to-Channel Isolation

The module architecture incorporates dual-redundant processing paths to deliver analog command signals across the 4-20 mA HART loop protocol. Digital configuration parameters are modulated onto the 4-20 mA analog signal, enabling automated asset management scanning without altering the primary analog variable. Built-in channel-to-channel isolation circuits prevent physical ground potential variations or single-loop electrical failures from propagating to adjacent output loops. This containment provides continuous noise immunity and signal conversion accuracy when the module handles real-time actuator positioning loops under harsh ambient cross-talk profiles.

Frequently Asked Questions

Q: What are the backplane load limitations and redundancy switching latency behaviors for this card?

A: The KJ3221X1-BA1 draws a fixed 150 mA from the 12 VDC LocalBus rail. When configured as a redundant pair on a compatible carrier assembly, an internal hardware voting matrix continuously monitors module health, enabling a Bumpless transfer latency to the standby card if a primary channel hardware fault or line disconnection occurs.

Q: How does the integrated physical keying mechanism prevent slot alignment errors during online replacement?

A: The module base interfaces with a matching terminal block set to mechanical key position A4. This physical obstruction architecture prevents the uncalibrated insertion of mismatched voltage or digital modules into a slot wired and designated strictly for 4-20 mA HART analog output circuitry.

Field Installation Guidelines

  • Verify that the target terminal block assembly is fixed to key position A4 before sliding the card into the slot structure.
  • Mount the module carrier assembly within a clean enclosure that limits particulate ingress to satisfy the ISA-S71.04-1985 Class G3 airborne contaminant standard.
  • Terminate all 4-20 mA current loops using shielded twisted-pair cables, bonding the overall braided shield to the single instrument earth bus bar.
  • Maintain physical isolation between low-voltage 24 VDC field circuit lines and heavy high-voltage AC power distribution cabling inside the cabinet layout.
  • Confirm that bussed field power lines provide a regulated 24 VDC up to the 300 mA full module rated capacity.