LG1093AA25 | Honeywell Safety Sensor for Boilers and Gas Turbines
LG1093AA25 | Honeywell Safety Sensor for Boilers and Gas Turbines
LG1093AA25 | Honeywell Safety Sensor for Boilers and Gas Turbines
/ 3

LG1093AA25 | Honeywell Safety Sensor for Boilers and Gas Turbines

  • Manufacturer: Honeywell

  • Part Number: LG1093AA25

  • Condition:New with Original Package

  • Product Type: Safety Sensor for Boilers and Gas Turbines

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Product Overview

The Honeywell LG1093AA25 is a high-performance UV flame sensor engineered for industrial combustion monitoring. It detects ultraviolet radiation emitted by hydrocarbon flames, providing reliable flame verification in boilers, gas turbines, and furnaces. Designed for rugged environments, this sensor features a fast response time, corrosion-resistant stainless steel construction, and EMI-shielded cabling, ensuring safe and efficient combustion control.

Technical Specifications

Specification Details
Model Number LG1093AA25
Sensor Type Geiger-Mueller-type phototube
Spectral Response 1800–2600 Å (UV solar-blind range)
Detection Range Up to 6 ft (1.8 m)
Field of View 90° wide-angle coverage
Response Time <200 milliseconds
Operating Temperature −40°F (−40°C) to +250°F (+121°C)
Window Pressure Rating 150 psig at 400°F (204°C)
Power Supply 260–350 VDC (provided by amplifier)
Signal Output 24 VDC standard
Power Consumption Approx. 5 W
Cable Length Standard 42 ft (12.8 m); customizable
Mounting Interface ¾-inch NPT internal thread; 1-inch conduit thread for shielded cable
Material Stainless steel (1.4571)
Environmental Protection Teflon-shielded cable, EMI-resistant, suitable for explosive atmospheres
Weight 4.3 lbs

FAQ

Q1: What type of flame does the LG1093AA25 detect?
A1: It detects ultraviolet radiation from hydrocarbon flames in industrial applications.

Q2: What is the maximum detection range?
A2: The sensor detects flames up to 6 ft (1.8 m) away.

Q3: What power supply does it require?
A3: The LG1093AA25 operates on 260–350 VDC provided by the amplifier.

Q4: Can it operate in extreme temperatures?
A4: Yes, it functions from −40°C to +121°C (−40°F to +250°F).

Q5: Is the cable shielded against electrical interference?
A5: Yes, it features a Teflon-shielded cable resistant to EMI.

 