Modicon Quantum 140AIO33000 8-Channel Output Module
Manufacturer: Schneider
-
Part Number: 140AIO33000
Condition:New with Original Package
Product Type: Intrinsically Safe Analog Output Module
-
Country of Origin: USA
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
Product Description
The Schneider Electric 140AIO33000 is an intrinsically safe analog output module developed for the Modicon Quantum automation platform. It is designed to drive field actuators located in hazardous areas while maintaining strict compliance with intrinsic safety requirements for Zone 20, 21, and 22 installations.
This module provides eight independent analog current outputs and is optimized for precise control of valves, positioners, and other current-driven devices. Integrated safety circuitry limits energy at the outputs, ensuring safe operation in explosive atmospheres without sacrificing control accuracy or response time.
With fast update and settling performance, 140AIO33000 supports closed-loop process control in demanding industries such as oil and gas, chemical processing, pharmaceuticals, and bulk materials handling. Configuration and diagnostics are handled through Schneider’s Quantum software environment, allowing straightforward integration into legacy systems. Although discontinued by the manufacturer, it remains in service as a replacement or spare module for installed Modicon Quantum systems.
Technical Specifications
| Parameter | Description |
|---|---|
| Model | 140AIO33000 |
| Manufacturer | Schneider Electric |
| Product Line | Modicon Quantum |
| Product Type | Intrinsically Safe Analog Output Module |
| Number of Outputs | 8 analog current outputs |
| Output Signal Ranges | 0–20 mA, 0–25 mA, 4–20 mA |
| Output Resolution | Up to 15-bit, range dependent |
| Maximum Loop Resistance | 500 Ω |
| Typical Accuracy | ±0.2% of full scale at 25 °C |
| Temperature Drift | 40 ppm/°C typical, ≤70 ppm/°C max |
| Linearity | ±1 LSB |
| Update Time | 4 ms |
| Settling Time | 1 ms to ±0.1% of final value |
| Fault Detection | Open-circuit detection for 4–20 mA |
| Channel-to-Bus Isolation | 1780 Vrms AC for 60 seconds |
| Power Dissipation | 12.5 W |
| Bus Current Requirement | 2.5 A |
| Protection | Internal fuse |
| Operating Temperature | 0 °C to +60 °C |
| Certifications | CE, ATEX II1 G/D EEx ia IIC |
| Configuration Software | Concept V2.2+, ProWORX, Unity Pro |
| Net Weight | 0.3 kg |
| Lifecycle Status | Discontinued (legacy Modicon Quantum) |