{"product_id":"modicon-quantum-power-supply-schneider-140cps12420","title":"Modicon Quantum Power Supply | Schneider 140CPS12420","description":"\u003ch2\u003eSchneider Electric 140CPS12420 Modicon Quantum Power Supply Module\u003c\/h2\u003e\n\u003cp\u003eThe \u003cstrong\u003e140CPS12420\u003c\/strong\u003e is a redundant AC power supply module for the Modicon Quantum automation platform. It accepts 115 VAC or 230 VAC inputs, delivers a 5.1 VDC output rated at 130 VA, and includes a green PWR OK status LED.\u003c\/p\u003e\n\u003ch3\u003eElectrical Ratings and Protection\u003c\/h3\u003e\n\u003cp\u003eInput current is 1100 mA at 115 VAC or 600 mA at 230 VAC, with startup inrush currents reaching 38 A at 115 VAC or 19 A at 230 VAC. Upstream or associated circuit protection uses a 2 A slow-blow fuse rating to handle startup surges and overload conditions.\u003c\/p\u003e\n\u003cp\u003eRated output power is 130 VA at 5.1 VDC for the Modicon Quantum rack. Because startup inrush reaches up to 38 A at 115 VAC, supply circuit and breaker sizing should account for transient turn-on current.\u003c\/p\u003e\n\u003ch3\u003eEnvironmental and Physical Limits\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003e140CPS12420\u003c\/strong\u003e operates from 0 to 60 deg C and up to 5000 m altitude, with relative humidity up to 95% without condensation. Storage temperature spans -40 to 85 deg C, and catalog weight is listed as 0.37 kg (0.81 lb), while descriptive text also notes 1.43 lb.\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003e140CPS12420\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Line\u003c\/td\u003e\n\u003ctd\u003eModicon Quantum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003ePower Supply Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Supply Type\u003c\/td\u003e\n\u003ctd\u003eRedundant\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Voltage\u003c\/td\u003e\n\u003ctd\u003e115 \/ 230 VAC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Current\u003c\/td\u003e\n\u003ctd\u003e1100 mA at 115 VAC, 600 mA at 230 VAC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInrush Current\u003c\/td\u003e\n\u003ctd\u003e38 A at 115 VAC, 19 A at 230 VAC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated Power\u003c\/td\u003e\n\u003ctd\u003e130 VA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Voltage\u003c\/td\u003e\n\u003ctd\u003e5.1 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAssociated Fuse Rating\u003c\/td\u003e\n\u003ctd\u003e2 A, slow-blow\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLocal Signalling\u003c\/td\u003e\n\u003ctd\u003e1 green LED for power (PWR OK)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAmbient Operating Temperature\u003c\/td\u003e\n\u003ctd\u003e0 to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAmbient Storage Temperature\u003c\/td\u003e\n\u003ctd\u003e-40 to 85 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Altitude\u003c\/td\u003e\n\u003ctd\u003e5000 m\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelative Humidity\u003c\/td\u003e\n\u003ctd\u003e95% without condensation\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eUPC\u003c\/td\u003e\n\u003ctd\u003e785901292654\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eGTIN\u003c\/td\u003e\n\u003ctd\u003e3595862017114\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.37 kg (0.81 lb)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: What AC input voltages and fuse rating apply to the 140CPS12420? A: It supports 115 VAC (1100 mA input current, 38 A inrush) and 230 VAC (600 mA input current, 19 A inrush), with an associated slow-blow fuse rating of 2 A.\u003c\/p\u003e\n\u003cp\u003eQ: What output and status indication does this power supply provide? A: It provides a 5.1 VDC output rated at 130 VA in a redundant power supply configuration and includes one green PWR OK LED for local status signalling.\u003c\/p\u003e\n\u003cp\u003eQ: What environmental limits are specified for operation and storage? A: Ambient operating temperature is 0 to 60 deg C up to 5000 m altitude with up to 95% non-condensing relative humidity, and storage temperature is -40 to 85 deg C.\u003c\/p\u003e","brand":"Schneider","offers":[{"title":"Default Title","offer_id":68017809981539,"sku":"140CPS1240","price":267.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0583\/5246\/8067\/files\/309._bf7299ab-3ca7-4102-a718-665e2120adf1.jpg?v=1795741697","url":"https:\/\/www.autocontrolglobal.com\/products\/modicon-quantum-power-supply-schneider-140cps12420","provider":"AutoControl Global","version":"1.0","type":"link"}