OCR1100 Emerson Ovation Datasheet & Technical Manual
OCR1100 Emerson Ovation Datasheet & Technical Manual
OCR1100 Emerson Ovation Datasheet & Technical Manual
/ 3

OCR1100 Emerson Ovation Datasheet & Technical Manual

  • Manufacturer: Emerson

  • Part Number: OCR1100

  • Condition:New with Original Package

  • Product Type: CPU Processors

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Emerson OCR1100 Ovation Controller

The Emerson OCR1100, also cataloged as the OCR1100 Controller, serves as the primary OCR1100 Controller utilized to execute serial and parallel I/O scanning across Ovation Distributed Control System platforms. The module executes deterministic algorithmic logic loops on an integrated Intel Atom Z510 processor core, coordinating real-time process data acquisition and state changes over local and virtual network boundaries.

Hardware Specifications

Parameter Specification
Model OCR1100
Brand Emerson
Origin USA
Weight Field industrial standard rating
Dimensions Compact footprint housing design
Operating Temp Field industrial standard rating
Power Consumption Low power fanless design consumption
Processor Intel Atom Z510, 1100 MHz
Memory 256 MB DRAM (expandable to 1 GB)
Storage 128 MB Compact Flash (expandable to 2 GB)
Direct I/O Capacity Up to 4,778 direct-wired I/O points
Virtual I/O Capacity Up to 8,192 virtual I/O points
SOE Capability Up to 1,024 Sequence of Events points per controller
Event Resolution 1 ms
Compliance IEC 61131-3, Achilles Level 1

Process Control and DCS Instrumentation Features

The OCR1100 manages up to 5 distinct control areas with software-selectable scan rates adjustable from 10 ms to 30,000 ms. Built with an architecture supporting automatic, non-interruptive failover between redundant controller pairs, it ensures constant process state execution in the event of primary module degradation. The onboard memory sub-tier uses 256 MB DRAM and 128 MB Compact Flash with SiSmart technology storage management. For tracking high-speed plant trips, the hardware logs up to 1,024 Sequence of Events (SOE) points natively with an internal event resolution of 1 ms.

Frequently Asked Questions

Q: How does the OCR1100 manage network security parameters for external data loops?

A: The controller features Achilles Level 1 certification, verifying that its integrated Ethernet communication stack has undergone cyber-security vulnerability testing against denial-of-service (DoS) vectors and boundary exploitation.

Q: What are the exact physical and virtual tag configuration boundaries per module?

A: A single hardware node handles a maximum threshold of 4,778 direct physical-wired I/O points alongside a maximum of 8,192 virtual I/O channels allocated for Ethernet-based third-party system integration.

Field Installation Guidelines

  • Redundant Pair Placement: Install the primary and secondary OCR1100 controllers in adjacent, dedicated slots on the Ovation backplane carrier. Connect the synchronization link cables completely to enable real-time mirror imaging of the runtime registries.
  • Compact Flash Handling: Only unseat or replace the internal Compact Flash storage media when the module power rail is completely isolated, or when standard engineering software tools have safely dismounted the storage subsystem.
  • Cabinet Ventilation Spacing: Though the fanless processor design minimizes active heat dissipation, maintain standard clear perimeter spacing inside the enclosure to allow natural convection currents to cool the outer metal fins.