Power Supply Module GE IC694PWR321B PACSystems RX3i
Power Supply Module GE IC694PWR321B PACSystems RX3i
Power Supply Module GE IC694PWR321B PACSystems RX3i
/ 3

Power Supply Module GE IC694PWR321B PACSystems RX3i

  • Manufacturer: GE Fanuc

  • Part Number: IC694PWR321B

  • Condition:New with Original Package

  • Product Type: Power Supply Modules

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

GE Fanuc IC694PWR321B PACSystems RX3i Power Supply Module

The GE Fanuc IC694PWR321B, also cataloged as the IC694PWR321 Power Supply Module, operates as a dedicated hardware component for regulated DC power conversion and backplane voltage delivery within PACSystems RX3i control platforms.

Hardware Specifications

Parameter Specification
Model IC694PWR321B
Brand GE Fanuc
Origin USA
Weight 0.68 kg
Dimensions 130 x 152 x 140 mm
Operating Temp 0 to +60 deg C
Power Consumption 30 W total power output
Input Voltage Nominal 120/240 VAC or 125 VDC
Input Voltage Range 85-264 VAC or 100-300 VDC
Input Frequency 47-63 Hz
DC Output Capacity +5 VDC (15 W max), Isolated +24 VDC (20 W max), Relay +24 VDC (15 W max)
Input Isolation 1500 VAC for 1 minute
Ride-Through Time 20 ms minimum
Protection Limits Internal 2 A input fuse, overvoltage, overcurrent, short-circuit protection

Backplane Bus Communication Velocity and Firmware Compatibility

The GE Fanuc IC694PWR321B converts universal input power into stable, regulated internal DC rails (+5 VDC, isolated +24 VDC, and relay +24 VDC) to maintain backplane bus communication velocity across PACSystems RX3i universal backplanes. Integrated line filtration and 1500 VAC galvanic input isolation prevent electrical noise from disrupting high-speed parallel bus signals. The module manages system power sequencing during power-up and brownout conditions, ensuring proper firmware flash compatibility across installed central processing units and high-density I/O modules without triggering memory corruption or false diagnostic faults.

Frequently Asked Questions

Q: Does the IC694PWR321B support field hot-swapping while the backplane is energized?

A: No. Installing or removing the power supply module while primary voltage is applied can cause backplane arc flash and damage internal logic components. De-energize all primary input power before servicing.

Q: How does the power supply handle brief voltage sags on the AC input line?

A: Internal hold-up capacitors provide a minimum ride-through time of 20 ms at full 30 W output load, allowing the processor to continue execution across single-cycle voltage drops without resetting.

Q: What happens if the combined system load exceeds the 30 W rated output limit?

A: Internal overcurrent protection circuitry activates, dropping output voltage levels to prevent thermal stress. This state triggers a logic fault signal across the backplane to initiate a controller shutdown sequence.

Field Installation Guidelines

  • Primary Supply De-energization: Turn off and lock out the main AC or DC feeder breaker before attaching input wiring to the module screw terminals.
  • Slot Alignment: Slide the power supply module into the leftmost dedicated slot of the RX3i baseplate until the rear connector latches securely into the backplane frame.
  • Terminal Wiring Separation: Route high-voltage AC or DC power conductors through separate conduit paths away from low-voltage signal cables to minimize electromagnetic coupling.
  • Grounding Connection: Connect a 14 AWG protective earth conductor directly from the module frame ground terminal to the enclosure master ground bus bar.
  • Convection Cooling Space: Maintain a minimum vertical distance of 100 mm above and below the module chassis to ensure unimpeded air circulation through the heat sink vents.