Premium Analog Input | Schneider TSXAEY1614 Modicon
Manufacturer: Schneider
-
Part Number: TSXAEY1614
Condition:New with Original Package
Product Type: Analog Input Modules
-
Country of Origin: USA
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
Schneider Electric TSXAEY1614 Modicon Premium Analog Input Module
The Schneider Electric TSXAEY1614 is a standard-format, 16-channel analog input module for the Modicon Premium programmable logic controller (PLC) platform. It acquires low-level voltage signals up to +/-80 mV and thermocouple inputs (types B, E, J, K, L, N, R, S, T, and U) with 16-bit analog-to-digital conversion and 70 ms nominal read cycle time per channel.
Thermocouple and Low-Level Signal Acquisition
Sixteen dedicated inputs accept thermocouple sensors or +/-80 mV low-level voltage signals for temperature and process monitoring. Because millivolt-level thermocouple outputs are sensitive to electrical noise and stray potentials, verify sensor type configuration, cold-junction handling, and shielded cabling during engineering setup.
With 16-bit resolution and a 70 ms nominal read cycle time per channel, scan timing scales across active channels. Check total loop update time against control loop requirements before assigning fast-changing temperature points.
Isolation, Wiring, and Environmental Limits
The module provides 1000 Vrms channel-to-bus and channel-to-ground isolation, rated for 250 V AC / 280 V AC common mode voltage and 250 V DC common mode to earth. Field connections use two 25-pin SUB-D connectors, and current draw from the rack is 300 mA at 5 V DC.
Mechanical and environmental ratings include a standard module format, IP20 ingress protection, approximate weight of 0.35 kg, operating temperature from 0 to 60 deg C, and storage temperature from -25 to 70 deg C. Keep panel wiring clear of high-voltage power conductors to preserve low-level signal integrity.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | TSXAEY1614 |
| Brand | Schneider Electric |
| Product Series | Modicon Premium |
| Product Type | Analog Input Module |
| Number of Inputs | 16 channels |
| Input Type | Thermocouple / Voltage |
| Thermocouple Types | B, E, J, K, L, N, R, S, T, U |
| Voltage Input Range | +/-80 mV |
| Analog-to-Digital Conversion | 16 bits |
| Nominal Read Cycle Time | 70 ms per channel |
| Channel-to-Bus Isolation | 1000 Vrms |
| Channel-to-Ground Isolation | 1000 Vrms |
| Common Mode Voltage | 250 V AC / 280 V AC |
| Common Mode to Earth | 250 V DC |
| Electrical Connection | 2 x 25-pin SUB-D connectors |
| Current Consumption | 300 mA at 5 V DC |
| Module Format | Standard |
| Operating Temperature | 0-60 deg C |
| Storage Temperature | -25-70 deg C |
| Ingress Protection | IP20 |
| Weight | Approximately 0.35 kg |
Frequently Asked Questions
Q: Which sensors and voltage signals can the TSXAEY1614 measure? A: It supports thermocouples of types B, E, J, K, L, N, R, S, T, and U as well as low-level voltage inputs up to +/-80 mV across 16 channels. Confirm channel configuration and sensor types match the connected probes in your Modicon Premium project.
Q: What wiring and isolation limits apply to the TSXAEY1614? A: Connections are made via two 25-pin SUB-D connectors, with 1000 Vrms channel-to-bus and channel-to-ground isolation, 250 V AC / 280 V AC common mode voltage, and 250 V DC common mode to earth. Verify connector pinouts, thermocouple extension wire matching, and common-mode voltage limits during installation.