Safety Manager Safe Analog Output | FC-TSAO-0220m Honeywell
Manufacturer: Honeywell
-
Part Number: FC-TSAO-0220
Condition:New with Original Package
Product Type: Safety Manager Safe Analog Output
-
Country of Origin: USA
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
Product Overview
The FC-TSAO-0220m (Model: FC-TSAO-0220m) is a high-integrity safe analog output module engineered for Honeywell Safety Manager®, FSC (Fail-Safe Controller), and Experion® PKS platforms. It is primarily utilized in Safety Instrumented Systems (SIS) to provide precise and reliable 0(4)–20 mA signals to critical field actuators, such as control valves and proportional positioning devices.
A key feature of the FC-TSAO-0220m (Part Number: FC-TSAO-0220m) is its integrated Field Termination Assembly (FTA) logic, which facilitates the interface between the system interconnection cable (SICC-0001/Lx) and external field wiring. The module supports HART communication on both channels, allowing for advanced device diagnostics and calibration. Furthermore, it allows for serial connection of up to eight modules to fully utilize the 16 channels of a HART multiplexer, ensuring comprehensive asset management in oil, gas, and power generation facilities.
Detailed Technical Specifications
The FC-TSAO-0220m is built to the following professional engineering standards:
-
Manufacturer: Honeywell (USA)
-
Model Number: FC-TSAO-0220m
-
Product Type: Safe Analog Output Module (HART Compatible)
-
Output Channels: 2 Independent analog output channels
-
Signal Range: Configurable 0–20 mA or 4–20 mA
-
Supply Voltage: 24 V DC nominal field supply
-
Maximum Output Voltage: 40 V DC (per IEC 1010)
-
Maximum Current: 25 mA per channel (IEC overvoltage category 3)
-
Accuracy: ±0.1 % of span at 25 °C; ±0.2 % across full temperature range
-
Resolution: 12-bit Digital-to-Analog Conversion (DAC)
-
Load Resistance: Up to 600 Ω (at 4–20 mA); Up to 1200 Ω (at 0–20 mA)
-
Response Time: < 10 ms typical
-
Diagnostics: Comprehensive detection of open-circuit, short-circuit, and power failure
-
Isolation: Full channel-to-channel and channel-to-ground electrical isolation
-
Operating Temperature: –20 °C to +70 °C (Industrial grade)
-
Dimensions: 12.7 cm x 12.7 cm x 12.7 cm (External enclosure)
-
Weight: 0.8 KG (Module with termination assembly)
-
Certifications: CE, UL, CSA, TUV (SIL Rated)