{"product_id":"schneider-electric-140aci03000c-modicon-quantum-input-module","title":"Schneider Electric 140ACI03000C Modicon Quantum Input Module","description":"\u003ch2\u003eSchneider Electric 140ACI03000C Modicon Quantum Analog Input Module\u003c\/h2\u003e\n\u003cp\u003eThe Schneider Electric \u003cstrong\u003e140ACI03000C\u003c\/strong\u003e is an 8-channel differential analog input module designed for the Modicon Quantum programmable logic controller (PLC) platform. Equipped with 12-bit analog-to-digital conversion and conformal coating, it acquires standard 1-5 VDC and 4-20 mA process signals while occupying 9 input words in the controller I\/O map.\u003c\/p\u003e\n\u003ch3\u003eSignal Acquisition and Input Protection\u003c\/h3\u003e\n\u003cp\u003eEach of the eight differential channels includes a single-pole low-pass filter with a 15 Hz (+\/-20% at -3 dB) cutoff frequency to attenuate high-frequency process noise, updating channels every 5 ms. The inputs withstand continuous overloads up to 50 VDC in voltage mode and 25 mA in current mode, supported by broken-wire and undervoltage fault diagnostics.\u003c\/p\u003e\n\u003ch3\u003eElectrical Isolation and Conformal Coating\u003c\/h3\u003e\n\u003cp\u003eTo prevent ground loops and protect backplane logic, the module provides 1000 VDC channel-to-bus isolation (tested to 3000 VDC for 60 seconds) and 30 VDC channel-to-channel isolation. The \u003cstrong\u003eC\u003c\/strong\u003e suffix designates factory-applied conformal coating on the printed circuit board assembly, protecting internal circuitry against corrosive atmospheres and humidity.\u003c\/p\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003e140ACI03000C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Series\u003c\/td\u003e\n\u003ctd\u003eModicon Quantum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eAnalog Input Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Channels\u003c\/td\u003e\n\u003ctd\u003e8\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Type\u003c\/td\u003e\n\u003ctd\u003eDifferential\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Signal Ranges\u003c\/td\u003e\n\u003ctd\u003e1-5 VDC, 4-20 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eResolution\u003c\/td\u003e\n\u003ctd\u003e12 bits\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAddressing Requirement\u003c\/td\u003e\n\u003ctd\u003e9 input words\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eChannel Update Time\u003c\/td\u003e\n\u003ctd\u003e5 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Impedance (Voltage)\u003c\/td\u003e\n\u003ctd\u003eGreater than 20 Mohm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Impedance (Current)\u003c\/td\u003e\n\u003ctd\u003e250 ohm +\/-0.01%\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Overload\u003c\/td\u003e\n\u003ctd\u003e50 VDC (voltage), 25 mA (current)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAbsolute Accuracy Error\u003c\/td\u003e\n\u003ctd\u003e+\/-0.05% of full scale\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Accuracy Error\u003c\/td\u003e\n\u003ctd\u003e+\/-0.1% of full scale\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLinearity Error\u003c\/td\u003e\n\u003ctd\u003e+\/-0.04%\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTemperature Drift\u003c\/td\u003e\n\u003ctd\u003e+\/-0.0025% FS\/deg C typical (+\/-0.005% FS\/deg C max)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommon Mode Rejection\u003c\/td\u003e\n\u003ctd\u003eGreater than 72 dB at 60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Filter\u003c\/td\u003e\n\u003ctd\u003eSingle-pole low-pass, 15 Hz +\/-20% (-3 dB)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation (Channel-to-Bus)\u003c\/td\u003e\n\u003ctd\u003e1000 VDC (3000 VDC dielectric test for 60 s)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation (Channel-to-Channel)\u003c\/td\u003e\n\u003ctd\u003e30 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFault Detection\u003c\/td\u003e\n\u003ctd\u003eBroken wire, undervoltage\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBus Current Requirement\u003c\/td\u003e\n\u003ctd\u003e240 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Dissipation\u003c\/td\u003e\n\u003ctd\u003e2 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStatus Indicators\u003c\/td\u003e\n\u003ctd\u003eGreen and red LEDs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSpecial Protection\u003c\/td\u003e\n\u003ctd\u003eConformal coating\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting Type\u003c\/td\u003e\n\u003ctd\u003eModicon Quantum PLC rack\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Weight\u003c\/td\u003e\n\u003ctd\u003e0.3 kg (Shipping weight: 1.5 kg)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003cp\u003eFrequently Asked Questions\u003c\/p\u003e\n\u003cp\u003eQ: What does the \"C\" suffix in 140ACI03000C indicate? A: The \u003cstrong\u003eC\u003c\/strong\u003e suffix indicates that the module is manufactured with conformal coating to protect its internal electronic components in harsh or corrosive industrial environments.\u003c\/p\u003e\n\u003cp\u003eQ: How many input words does the 140ACI03000C require in the PLC memory map? A: This 8-channel module requires 9 input words of I\/O addressing space in a Modicon Quantum controller configuration.\u003c\/p\u003e\n\u003cp\u003eQ: What input signal types and fault diagnostics are supported on each channel? A: The module accepts 1-5 VDC and 4-20 mA differential signals and provides built-in detection for broken-wire and undervoltage conditions.\u003c\/p\u003e","brand":"Schneider","offers":[{"title":"Default Title","offer_id":67940137468003,"sku":"140ACI03000C","price":260.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0583\/5246\/8067\/files\/293_9a4f18d6-f848-47e1-a829-86cf1c50f395.jpg?v=1794793576","url":"https:\/\/www.autocontrolglobal.com\/products\/schneider-electric-140aci03000c-modicon-quantum-input-module","provider":"AutoControl Global","version":"1.0","type":"link"}