Schneider Electric 140DAI54300 Quantum 115VAC Input Module
Schneider Electric 140DAI54300 Quantum 115VAC Input Module
Schneider Electric 140DAI54300 Quantum 115VAC Input Module
/ 3

Schneider Electric 140DAI54300 Quantum 115VAC Input Module

  • Manufacturer: Schneider

  • Part Number: 140DAI54300

  • Condition:New with Original Package

  • Product Type: AC Discrete Input Modules

  • Country of Origin: France

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Schneider Electric 140DAI54300 Modicon Quantum AC Discrete Input Module

The 140DAI54300 is a 16-channel, 115 VAC discrete input module for the Modicon Quantum PLC platform. Arranged in two isolated groups of eight channels for 47-63 Hz AC signals, it connects to field switches, limit switches, and contacts via a 140XTS00200 terminal block. It uses one input word in PLC addressing and provides 16 input status LEDs plus bus and fault indicators.

Input Thresholds, Impedance, and Response

Guaranteed ON-state (state 1) voltage is 79-132 VAC at 57-63 Hz and 85-132 VAC at 47-53 Hz, while guaranteed OFF-state (state 0) voltage is 0-20 VAC. Because capacitive input impedance scales with frequency (12 kOhm at 57-63 Hz and 14.4 kOhm at 47-53 Hz), nominal input current is 11.1 mA at 57-63 Hz and 13.2 mA at 47-53 Hz, with a maximum allowable leakage current of 2.1 mA.

Switching limits allow up to 132 VAC continuous input, 156 VAC for 10 seconds, and 200 VAC for 1 cycle. OFF-to-ON response takes 0.75-4.9 line cycles and ON-to-OFF response takes 7.3-12.3 ms, which affects pulse capture and de-energization timing on AC circuits.

Isolation, Power, and Diagnostics

Group-to-group isolation and group-to-bus isolation are both rated at 1780 Vrms for 1 minute, separating each 8-channel group and the PLC backplane from field wiring transients. Field wiring terminates on a 140XTS00200 terminal block within a standard module format weighing 0.3 kg.

The module draws 180 mA from the backplane bus with up to 5.5 W power dissipation and occupies one input word in controller memory. Local LEDs indicate individual channel states (16 green LEDs), active bus communication (1 green LED), and external faults (1 red LED), and configuration is supported in Unity Pro, Concept, and ProWORX 32.

Technical Specifications

Parameter Specification
Model 140DAI54300
Brand Schneider Electric
Product Series / Range Modicon Quantum
Product Type AC Discrete Input Module (VAC discrete input modules)
Number of Inputs 16 Channels (2 groups of 8 channels)
Input Voltage 115 VAC nominal (47-63 Hz)
ON-State Voltage 79-132 VAC at 57-63 Hz; 85-132 VAC at 47-53 Hz
OFF-State Voltage 0-20 VAC
Input Current 11.1 mA at 57-63 Hz; 13.2 mA at 47-53 Hz
Input Impedance 12 kOhm capacitive at 57-63 Hz; 14.4 kOhm capacitive at 47-53 Hz
Maximum Leakage Current 2.1 mA
Maximum Input Voltage 132 VAC continuous; 156 VAC (10 s); 200 VAC (1 cycle)
OFF-to-ON Response Time 0.75-4.9 line cycles
ON-to-OFF Response Time 7.3-12.3 ms
Group-to-Group Isolation 1780 Vrms for 1 minute
Group-to-Bus Isolation 1780 Vrms for 1 minute
Bus Current Requirement 180 mA
Maximum Power Dissipation 5.5 W
Addressing Requirement 1 Input Word
Connection Type 140XTS00200 Terminal Block
Local Signalling 16 input LEDs (green), 1 bus active LED (green), 1 external fault LED (red)
Module Format Standard
Programming Software Unity Pro, Concept, ProWORX 32
Marking CE
Weight 0.3 kg

Frequently Asked Questions

Q: How are the 16 AC inputs grouped and wired on the 140DAI54300? A: The 16 channels are divided into two groups of eight and connect via a 140XTS00200 terminal block. Keep each group's wiring isolated from the other group and within the 1780 Vrms for 1 minute isolation rating.

Q: Why do input current and impedance vary with line frequency on this module? A: The input circuit presents a capacitive impedance of 12 kOhm at 57-63 Hz and 14.4 kOhm at 47-53 Hz, causing input current to shift from 11.1 mA to 13.2 mA. Account for this shift and the 2.1 mA maximum leakage current when wiring switches or triac/leakage-prone field devices.

Q: Which engineering software supports the 140DAI54300? A: It is supported in Unity Pro, Concept, and ProWORX 32 for Modicon Quantum systems. Confirm your project toolset and 1-input-word addressing assignment during hardware configuration.