{"product_id":"schneider-electric-140dai54300-quantum-115vac-input-module","title":"Schneider Electric 140DAI54300 Quantum 115VAC Input Module","description":"\u003ch2\u003eSchneider Electric 140DAI54300 Modicon Quantum AC Discrete Input Module\u003c\/h2\u003e\n\u003cp\u003eThe \u003cstrong\u003e140DAI54300\u003c\/strong\u003e is a 16-channel, 115 VAC discrete input module for the Modicon Quantum PLC platform. Arranged in two isolated groups of eight channels for 47-63 Hz AC signals, it connects to field switches, limit switches, and contacts via a 140XTS00200 terminal block. It uses one input word in PLC addressing and provides 16 input status LEDs plus bus and fault indicators.\u003c\/p\u003e\n\u003ch3\u003eInput Thresholds, Impedance, and Response\u003c\/h3\u003e\n\u003cp\u003eGuaranteed ON-state (state 1) voltage is 79-132 VAC at 57-63 Hz and 85-132 VAC at 47-53 Hz, while guaranteed OFF-state (state 0) voltage is 0-20 VAC. Because capacitive input impedance scales with frequency (12 kOhm at 57-63 Hz and 14.4 kOhm at 47-53 Hz), nominal input current is 11.1 mA at 57-63 Hz and 13.2 mA at 47-53 Hz, with a maximum allowable leakage current of 2.1 mA.\u003c\/p\u003e\n\u003cp\u003eSwitching limits allow up to 132 VAC continuous input, 156 VAC for 10 seconds, and 200 VAC for 1 cycle. OFF-to-ON response takes 0.75-4.9 line cycles and ON-to-OFF response takes 7.3-12.3 ms, which affects pulse capture and de-energization timing on AC circuits.\u003c\/p\u003e\n\u003ch3\u003eIsolation, Power, and Diagnostics\u003c\/h3\u003e\n\u003cp\u003eGroup-to-group isolation and group-to-bus isolation are both rated at 1780 Vrms for 1 minute, separating each 8-channel group and the PLC backplane from field wiring transients. Field wiring terminates on a \u003cstrong\u003e140XTS00200\u003c\/strong\u003e terminal block within a standard module format weighing 0.3 kg.\u003c\/p\u003e\n\u003cp\u003eThe module draws 180 mA from the backplane bus with up to 5.5 W power dissipation and occupies one input word in controller memory. Local LEDs indicate individual channel states (16 green LEDs), active bus communication (1 green LED), and external faults (1 red LED), and configuration is supported in Unity Pro, Concept, and ProWORX 32.\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003e140DAI54300\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Series \/ Range\u003c\/td\u003e\n\u003ctd\u003eModicon Quantum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eAC Discrete Input Module (VAC discrete input modules)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Inputs\u003c\/td\u003e\n\u003ctd\u003e16 Channels (2 groups of 8 channels)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Voltage\u003c\/td\u003e\n\u003ctd\u003e115 VAC nominal (47-63 Hz)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eON-State Voltage\u003c\/td\u003e\n\u003ctd\u003e79-132 VAC at 57-63 Hz; 85-132 VAC at 47-53 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOFF-State Voltage\u003c\/td\u003e\n\u003ctd\u003e0-20 VAC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Current\u003c\/td\u003e\n\u003ctd\u003e11.1 mA at 57-63 Hz; 13.2 mA at 47-53 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Impedance\u003c\/td\u003e\n\u003ctd\u003e12 kOhm capacitive at 57-63 Hz; 14.4 kOhm capacitive at 47-53 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Leakage Current\u003c\/td\u003e\n\u003ctd\u003e2.1 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Input Voltage\u003c\/td\u003e\n\u003ctd\u003e132 VAC continuous; 156 VAC (10 s); 200 VAC (1 cycle)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOFF-to-ON Response Time\u003c\/td\u003e\n\u003ctd\u003e0.75-4.9 line cycles\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eON-to-OFF Response Time\u003c\/td\u003e\n\u003ctd\u003e7.3-12.3 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eGroup-to-Group Isolation\u003c\/td\u003e\n\u003ctd\u003e1780 Vrms for 1 minute\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eGroup-to-Bus Isolation\u003c\/td\u003e\n\u003ctd\u003e1780 Vrms for 1 minute\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBus Current Requirement\u003c\/td\u003e\n\u003ctd\u003e180 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Power Dissipation\u003c\/td\u003e\n\u003ctd\u003e5.5 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAddressing Requirement\u003c\/td\u003e\n\u003ctd\u003e1 Input Word\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConnection Type\u003c\/td\u003e\n\u003ctd\u003e140XTS00200 Terminal Block\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLocal Signalling\u003c\/td\u003e\n\u003ctd\u003e16 input LEDs (green), 1 bus active LED (green), 1 external fault LED (red)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Format\u003c\/td\u003e\n\u003ctd\u003eStandard\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProgramming Software\u003c\/td\u003e\n\u003ctd\u003eUnity Pro, Concept, ProWORX 32\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMarking\u003c\/td\u003e\n\u003ctd\u003eCE\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.3 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: How are the 16 AC inputs grouped and wired on the 140DAI54300? A: The 16 channels are divided into two groups of eight and connect via a 140XTS00200 terminal block. Keep each group's wiring isolated from the other group and within the 1780 Vrms for 1 minute isolation rating.\u003c\/p\u003e\n\u003cp\u003eQ: Why do input current and impedance vary with line frequency on this module? A: The input circuit presents a capacitive impedance of 12 kOhm at 57-63 Hz and 14.4 kOhm at 47-53 Hz, causing input current to shift from 11.1 mA to 13.2 mA. Account for this shift and the 2.1 mA maximum leakage current when wiring switches or triac\/leakage-prone field devices.\u003c\/p\u003e\n\u003cp\u003eQ: Which engineering software supports the 140DAI54300? A: It is supported in Unity Pro, Concept, and ProWORX 32 for Modicon Quantum systems. Confirm your project toolset and 1-input-word addressing assignment during hardware configuration.\u003c\/p\u003e","brand":"Schneider","offers":[{"title":"Default Title","offer_id":68014188101731,"sku":"140DAI54300","price":267.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0583\/5246\/8067\/files\/435._bce3096e-84c9-4438-904e-70c21a46440a.jpg?v=1795683097","url":"https:\/\/www.autocontrolglobal.com\/products\/schneider-electric-140dai54300-quantum-115vac-input-module","provider":"AutoControl Global","version":"1.0","type":"link"}