Schneider Electric 170ANR12091 Modicon Momentum I/O Base
Schneider Electric 170ANR12091 Modicon Momentum I/O Base
Schneider Electric 170ANR12091 Modicon Momentum I/O Base
/ 3

Schneider Electric 170ANR12091 Modicon Momentum I/O Base

  • Manufacturer: Schneider

  • Part Number: 170ANR12091

  • Condition:New with Original Package

  • Product Type: I/O Base Modules

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Schneider Electric 170ANR12091 Modicon Momentum Analog/Discrete I/O Base

The Schneider Electric 170ANR12091 is a mixed-signal I/O base module designed for the Modicon Momentum distributed automation platform. It combines 6 analog inputs, 4 analog outputs, 8 discrete inputs, and 8 discrete outputs in a single unit. Built for 24 VDC control systems, this base interfaces field sensors and actuators with top-mounted Momentum communication adapters or processors.

Technical Specifications

Parameter Specification
Model 170ANR12091
Brand Schneider Electric
Product Series Modicon Momentum
Product Type Analog/Discrete I/O Base
Analog Input Channels 6 single-ended channels (1 group)
Analog Input Signal Range +/- 10 VDC
Analog Input Resolution 14 bits
Analog Input Resistance > 1 MOhm
Max Analog Input Voltage <= 15 V
Analog Input Conversion Time <= 0.75 ms
Analog Output Channels 4 channels (1 group)
Analog Output Signal Range +/- 10 VDC
Analog Output Resolution 14 bits
Analog Output Load Impedance >= 2 kOhm
Analog Output Conversion Time 1.2 ms
Analog Output Conversion Error +/- 0.4 % at 25 deg C
Discrete Input Channels 8 channels (2 groups of 4), IEC 1131-2 Type 2
Discrete Input Voltage 24 VDC (3 to 32 V limits)
Discrete Input Logic Positive logic (State 1 >= 11 V / >= 6 mA; State 0 <= 5 V / <= 2 mA)
Discrete Input Overvoltage 45 V for 10 s
Discrete Input Response Time 1.2 ms (state 0 to 1 and state 1 to 0)
Discrete Output Channels 8 channels (1 group), positive logic transistor
Discrete Output Voltage 10 to 30 VDC
Discrete Output Current 0.25 A per point, 2 A per group, 2 A per module
Discrete Output Protection Short-circuit and overload protection
Discrete Output Response Time 1.2 ms (state 0 to 1), 1.05 ms (state 1 to 0)
Rated Supply Voltage 24 VDC (19.2 to 30 VDC range)
Current Consumption 400 mA at 24 VDC
Power Dissipation <= 6 W
Isolation Voltage 500 V for 1 min (between analog I/O and operating voltage; between operating voltage and I/O to ground)
Electrical Connection 2 connectors for removable terminal blocks
Local Signaling 8 channel status LEDs
Dimensions (W x D x H) 141.5 mm x 47.5 mm x 125 mm
Operating Temperature 0 to 60 deg C
Storage Temperature -40 to 85 deg C
Relative Humidity 95 % without condensation
Operating Altitude <= 5000 m

Signal Architecture and Grounding

The analog section handles bipolar +/- 10 VDC voltage signals across 6 single-ended inputs and 4 outputs at 14-bit resolution. Analog outputs provide configurable fail-state behavior, allowing the channel to either hold its last value or reset to zero upon fault detection.

The discrete section operates on 24 VDC positive logic. The 8 inputs are split into two isolated groups of 4 and meet IEC 1131-2 Type 2 thresholds. The 8 transistor outputs are arranged in a single group rated at 0.25 A per point and 2 A maximum total load, incorporating built-in short-circuit and overload protection.

Internally, analog ground (AGND) and digital ground (DGND) tie together at a single common point inside the base. Field wiring must strictly observe this separation: external digital input circuits return to the DGND terminal, while external analog circuits return to AGND terminals to prevent ground loops and signal noise.

Wiring and Platform Integration

The 170ANR12091 forms the lower hardware layer of a Modicon Momentum node and requires a snap-on top adapter—such as a fieldbus communication adapter or processor module—to communicate with a host controller.

Field wiring connects through two front-facing ports designed for removable terminal blocks. Per manufacturer wiring diagrams, external fusing is specified for circuit protection: 1 A fuses on power/analog supply lines (F1, F3) and a 2.5 A fuse on the discrete output supply line (F2).

Frequently Asked Questions

Q: Does the 170ANR12091 support 4-20 mA current signals on its analog channels? A: No. Both the 6 analog inputs and 4 analog outputs are hardware-configured strictly for +/- 10 VDC voltage signals.

Q: Can the 170ANR12091 operate as a standalone remote I/O station without additional hardware? A: No. As an I/O base module, it requires a compatible Modicon Momentum communication adapter or processor snapped onto its top connector, as well as removable terminal blocks for field wiring.

Q: How should analog and discrete ground wires be terminated on this module?A: External analog circuits must return exclusively to the AGND terminals, and external digital inputs must return to the DGND terminal. Although AGND and DGND connect internally at a single point, keeping field returns separate prevents digital switching noise from affecting analog accuracy.