Schneider Electric ACE949-2 Sepam RS485 Network Interface
Manufacturer: Schneider
-
Part Number: ACE949-2
Condition:New with Original Package
Product Type: Communication Interfaces
-
Country of Origin: France
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
Schneider Electric ACE949-2 Sepam RS485 Communication Interface
The Schneider Electric ACE949-2 (commercial reference 59642) is a 2-wire RS485 network interface module for Sepam protection relays. It connects Sepam Series 20, 40, 48, 60, and 80 relays to Modbus RTU networks over E-LAN and S-LAN topologies while serving as a network cable branching point via the CCA612 connection cable. The module runs on a 12 VDC or 24 VDC supply and mounts on a symmetrical DIN rail.
Network Function and System Compatibility
The ACE949-2 establishes the physical and electrical 2-wire RS485 link between a Sepam protection relay and a supervisory Modbus RTU bus. In multi-drop serial architectures, it acts as a trunk-line branching point so individual relays can be wired onto the network without breaking the main bus run.
- Compatible with Sepam Series 20, 40, 48, 60, and 80 protection relays.
- Supports Modbus RTU communication across E-LAN and S-LAN network interfaces.
- Pairs with the CCA612 connection cable for relay-to-interface interconnection.
- Includes a front-face LED for local link-activity indication.
Power and Mounting Requirements
The interface accepts a distributed DC power supply at 12 VDC +/-10% or 24 VDC +/-10%. Current draw is 16 mA in receive mode and rises to 40 mA maximum during data transmission, which helps size shared auxiliary DC supplies on multi-relay panels.
Housed in a compact 88 x 72 x 30 mm (H x W x D) enclosure, the unit fixes onto a symmetrical DIN rail inside relay compartments or switchgear panels.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | ACE949-2 |
| Commercial Reference | 59642 |
| Brand | Schneider Electric |
| Product Series | Sepam |
| Product Type | 2-Wire RS485 Communication Interface |
| Communication Interface | RS485, 2-wire |
| Communication Protocol | Modbus RTU |
| Network Interfaces | E-LAN, S-LAN |
| Compatible Relays | Sepam Series 20, 40, 48, 60, 80 |
| Compatible Connection Cable | CCA612 |
| Rated Supply Voltage | 12 VDC +/-10% or 24 VDC +/-10% |
| Current Consumption | 16 mA (receive mode), 40 mA max (transmit mode) |
| Local Indication | Front-face link-activity LED |
| Mounting | Fixed, symmetrical DIN rail |
| Dimensions (H x W x D) | 88 x 72 x 30 mm |
| Net Weight | 0.1 kg (0.2 kg listed in first source) |
| Operating Temperature | -25 deg C to +70 deg C (legacy installation documentation) |
Frequently Asked Questions
Q: Which Sepam protection relays and cables work with the ACE949-2? A: The ACE949-2 connects to Sepam Series 20, 40, 48, 60, and 80 protection relays and uses the CCA612 connection cable for relay interconnection and network branching.
Q: What power supply voltage and current does the ACE949-2 require? A: It operates from either a 12 VDC +/-10% or 24 VDC +/-10% distributed power supply, drawing 16 mA in receive mode and up to 40 mA during transmission.
Q: Which communication protocols and network types are supported? A: The module provides a 2-wire RS485 interface supporting the Modbus RTU protocol over E-LAN and S-LAN networks.