Schneider Electric BMXAMI0800 Modicon X80 Analog Input Module
Schneider Electric BMXAMI0800 Modicon X80 Analog Input Module
Schneider Electric BMXAMI0800 Modicon X80 Analog Input Module
/ 3

Schneider Electric BMXAMI0800 Modicon X80 Analog Input Module

  • Manufacturer: Schneider

  • Part Number: BMXAMI0800RU

  • Condition:New with Original Package

  • Product Type: Analog Input Modules

  • Country of Origin: France

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Schneider Electric BMXAMI0800 Modicon X80 Analog Input Module

The Schneider Electric BMXAMI0800 is an 8-channel, non-isolated high-level analog input module for the Modicon X80 automation platform. It acquires voltage and current signals from industrial field transmitters and sensors for process monitoring and control. Supporting multiple unipolar and bipolar ranges with 16-bit analog-to-digital conversion and configurable first-order digital filtering, it fits high-density analog signal acquisition where individual channel isolation is not required.

Signal Acquisition and Channel Architecture

Each of the eight high-level input channels accepts voltage or current signals, with input resolution specified as 15 bits plus sign from a 16-bit analog-to-digital converter. Voltage inputs present a 10 MOhm input impedance, while current inputs terminate across a 250 Ohm input resistance to convert loop current into a measurable voltage drop.

Because channels share a non-isolated design rather than per-channel isolation, engineers must pay attention to common ground references and potential ground loops across connected field instruments. First-order digital filtering helps suppress high-frequency noise on measurement lines before values are passed to the controller scan.

Scan Timing and Wiring Considerations

In fast read mode, total acquisition time scales with active channels according to 1 ms + 1 ms multiplied by the number of channels used, reaching 9 ms for an 8-channel read cycle. Matching filter settings and scan timing to process dynamics helps balance noise rejection against loop response speed.

Field wiring connects through a single 28-way connector on the module. Standardizing sensor signal conditioning and verifying ground referencing across the 28-way termination helps maintain measurement consistency during commissioning and maintenance.

Technical Specifications

Parameter Specification
Model BMXAMI0800
Brand Schneider Electric
Product Range Modicon X80
Product Type Analog input module
Number of Inputs 8 (high level)
Input Type Voltage and current
Voltage Input Ranges +-10 V, +-5 V, 0-10 V, 0-5 V, 1-5 V
Current Input Ranges +-20 mA, 0-20 mA, 4-20 mA
A/D Conversion 16 bits
Input Resolution 15 bits + sign
Input Impedance 10 MOhm (voltage)
Current Input Resistance 250 Ohm
Channel Isolation Non-isolated
Electrical Connection 1 x 28-way connector
Filter Type First-order digital filtering
Fast Read Cycle 1 ms + 1 ms x number of channels used
Read Cycle (8 Channels) 9 ms
Operating Temperature 0-60 deg C
Protection Rating IP20
Dimensions 2.5 cm x 10.2 cm x 7.6 cm (1.0 in x 4.0 in x 3.0 in)
Weight 0.186 kg (raw listing also notes 0.1 kg / 0 lbs 5.0 oz)
Country of Manufacture France
Tariff Code 8538907080

Frequently Asked Questions

Q: Does the BMXAMI0800 provide electrical isolation between individual analog channels? A: No, channel isolation is non-isolated. You should verify ground potential differences and reference wiring across connected field transmitters to avoid measurement errors or ground loops.

Q: Which voltage and current signals can each input channel accept? A: The module supports voltage ranges of +-10 V, +-5 V, 0-10 V, 0-5 V, and 1-5 V, as well as current ranges of +-20 mA, 0-20 mA, and 4-20 mA. Confirm the selected range and scaling match the transmitter output and the 250 Ohm current input resistance or 10 MOhm voltage input impedance.

Q: How long does it take to read all eight channels? A: Under the specified fast read cycle formula (1 ms + 1 ms x number of channels used), an 8-channel read cycle takes 9 ms. Actual system update behavior also depends on controller task scheduling and first-order digital filter configuration.

You may also like