{"product_id":"schneider-electric-bmxami0800-modicon-x80-analog-input-module","title":"Schneider Electric BMXAMI0800 Modicon X80 Analog Input Module","description":"\u003ch2\u003eSchneider Electric BMXAMI0800 Modicon X80 Analog Input Module\u003c\/h2\u003e\n\u003cp\u003eThe Schneider Electric \u003cstrong\u003eBMXAMI0800\u003c\/strong\u003e is an 8-channel, non-isolated high-level analog input module for the Modicon X80 automation platform. It acquires voltage and current signals from industrial field transmitters and sensors for process monitoring and control. Supporting multiple unipolar and bipolar ranges with 16-bit analog-to-digital conversion and configurable first-order digital filtering, it fits high-density analog signal acquisition where individual channel isolation is not required.\u003c\/p\u003e\n\u003ch3\u003eSignal Acquisition and Channel Architecture\u003c\/h3\u003e\n\u003cp\u003eEach of the eight high-level input channels accepts voltage or current signals, with input resolution specified as 15 bits plus sign from a 16-bit analog-to-digital converter. Voltage inputs present a 10 MOhm input impedance, while current inputs terminate across a 250 Ohm input resistance to convert loop current into a measurable voltage drop.\u003c\/p\u003e\n\u003cp\u003eBecause channels share a non-isolated design rather than per-channel isolation, engineers must pay attention to common ground references and potential ground loops across connected field instruments. First-order digital filtering helps suppress high-frequency noise on measurement lines before values are passed to the controller scan.\u003c\/p\u003e\n\u003ch3\u003eScan Timing and Wiring Considerations\u003c\/h3\u003e\n\u003cp\u003eIn fast read mode, total acquisition time scales with active channels according to 1 ms + 1 ms multiplied by the number of channels used, reaching 9 ms for an 8-channel read cycle. Matching filter settings and scan timing to process dynamics helps balance noise rejection against loop response speed.\u003c\/p\u003e\n\u003cp\u003eField wiring connects through a single 28-way connector on the module. Standardizing sensor signal conditioning and verifying ground referencing across the 28-way termination helps maintain measurement consistency during commissioning and maintenance.\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eBMXAMI0800\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Range\u003c\/td\u003e\n\u003ctd\u003eModicon X80\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eAnalog input module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Inputs\u003c\/td\u003e\n\u003ctd\u003e8 (high level)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Type\u003c\/td\u003e\n\u003ctd\u003eVoltage and current\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eVoltage Input Ranges\u003c\/td\u003e\n\u003ctd\u003e+-10 V, +-5 V, 0-10 V, 0-5 V, 1-5 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCurrent Input Ranges\u003c\/td\u003e\n\u003ctd\u003e+-20 mA, 0-20 mA, 4-20 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA\/D Conversion\u003c\/td\u003e\n\u003ctd\u003e16 bits\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Resolution\u003c\/td\u003e\n\u003ctd\u003e15 bits + sign\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Impedance\u003c\/td\u003e\n\u003ctd\u003e10 MOhm (voltage)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCurrent Input Resistance\u003c\/td\u003e\n\u003ctd\u003e250 Ohm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eChannel Isolation\u003c\/td\u003e\n\u003ctd\u003eNon-isolated\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eElectrical Connection\u003c\/td\u003e\n\u003ctd\u003e1 x 28-way connector\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFilter Type\u003c\/td\u003e\n\u003ctd\u003eFirst-order digital filtering\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFast Read Cycle\u003c\/td\u003e\n\u003ctd\u003e1 ms + 1 ms x number of channels used\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRead Cycle (8 Channels)\u003c\/td\u003e\n\u003ctd\u003e9 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e0-60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProtection Rating\u003c\/td\u003e\n\u003ctd\u003eIP20\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e2.5 cm x 10.2 cm x 7.6 cm (1.0 in x 4.0 in x 3.0 in)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.186 kg (raw listing also notes 0.1 kg \/ 0 lbs 5.0 oz)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCountry of Manufacture\u003c\/td\u003e\n\u003ctd\u003eFrance\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTariff Code\u003c\/td\u003e\n\u003ctd\u003e8538907080\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: Does the BMXAMI0800 provide electrical isolation between individual analog channels? A: No, channel isolation is non-isolated. You should verify ground potential differences and reference wiring across connected field transmitters to avoid measurement errors or ground loops.\u003c\/p\u003e\n\u003cp\u003eQ: Which voltage and current signals can each input channel accept? A: The module supports voltage ranges of +-10 V, +-5 V, 0-10 V, 0-5 V, and 1-5 V, as well as current ranges of +-20 mA, 0-20 mA, and 4-20 mA. Confirm the selected range and scaling match the transmitter output and the 250 Ohm current input resistance or 10 MOhm voltage input impedance.\u003c\/p\u003e\n\u003cp\u003eQ: How long does it take to read all eight channels? A: Under the specified fast read cycle formula (1 ms + 1 ms x number of channels used), an 8-channel read cycle takes 9 ms. Actual system update behavior also depends on controller task scheduling and first-order digital filter configuration.\u003c\/p\u003e","brand":"Schneider","offers":[{"title":"Default Title","offer_id":68001130545251,"sku":"BMXAMI0800RU","price":267.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0583\/5246\/8067\/files\/597..jpg?v=1795515427","url":"https:\/\/www.autocontrolglobal.com\/products\/schneider-electric-bmxami0800-modicon-x80-analog-input-module","provider":"AutoControl Global","version":"1.0","type":"link"}