Schneider Electric TWDXCAISO Modicon Twido Serial Link Tap Isolation Box
The Schneider Electric TWDXCAISO is an RS485 serial link tap isolation box engineered for Modicon Twido programmable logic controllers and Modicon M238 logic controllers. Powered by an external 24 VDC supply, it provides electrical isolation along with integrated line polarization and termination to stabilize Modbus serial communication links.
Signal Conditioning and Electrical Isolation
In multi-drop RS485 networks, potential differences and electrical noise can disrupt data transmission or damage controller communication ports. The TWDXCAISO isolates the RS485 bus and incorporates pre-polarization using two 620 ohm resistors alongside an RC line-end termination circuit rated at 120 ohm and 1 nF to suppress signal reflections.
Hardware Interfaces and Mounting
The unit provides two RJ45 connectors for serial bus patching and one screw terminal block for external power and field wiring connections. Weighing 0.1 kg, its housing clips directly onto a standard 35 mm symmetrical DIN rail inside control cabinets.
| Parameter | Specification |
|---|---|
| Model | TWDXCAISO |
| Brand | Schneider Electric |
| Product Range | Modicon Twido |
| Product Type | Serial Link Tap Isolation Box |
| Communication Interface | RS485 (Modbus) |
| Compatible Controllers | Modicon Twido PLC, Modicon M238 |
| Rated Supply Voltage | 24 VDC (external) |
| Connectors | 2 x RJ45, 1 x screw terminal block |
| Line Polarization | 2 x 620 ohm resistors |
| Line Termination | RC 120 ohm, 1 nF |
| Mounting Type | 35 mm symmetrical DIN rail |
| Net Weight | 0.1 kg |
| GTIN / EAN | 3595863895360 |
| Country of Origin | Indonesia |
Frequently Asked Questions
Q: Does the TWDXCAISO draw operating power directly from the PLC communication port? A: No, it requires an external 24 VDC power supply connected via its screw terminal block to power the internal RS485 isolation circuitry.
Q: What line polarization and termination values are built into the TWDXCAISO? A: The isolation box includes two 620 ohm resistors for line polarization and an RC line-end termination network consisting of a 120 ohm resistor and a 1 nF capacitor.
Q: Which Schneider Electric controllers are compatible with this isolation box? A: It is designed for use with Modicon Twido programmable controllers and Modicon M238 logic controllers.