Triconex Tricon P13381 Pulse Input Module
Triconex Tricon P13381 Pulse Input Module
Triconex Tricon P13381 Pulse Input Module
/ 3

Triconex Tricon P13381 Pulse Input Module

  • Manufacturer: Triconex

  • Part Number: PI3381

  • Condition:New with Original Package

  • Product Type: Pulse Input Modules

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Triconex P13381 Pulse Input Module

The Triconex P13381, also cataloged as the P13381 Pulse Input Module, operates as a dedicated hardware component for capturing speed and frequency measurements from rotating machinery sensors within Triconex Tricon Safety Instrumented System platforms.

Hardware Specifications

Parameter Specification
Model P13381
Brand Triconex
Origin USA
Weight Standard Chassis Module Weight
Dimensions Standard Tricon Chassis Slot Format
Operating Temp -20 to +65 deg C
Power Consumption System Backplane Powered
Product Type Pulse Input Modules
System Compatibility Triconex Tricon Safety Instrumented System
Input Channels 6 pulse inputs, channel isolated
Sensor Types Magnetic, active, open collector
Input Configuration Differential or single-ended
Speed Measurement Range 0 to 32000 RPM
Input Frequency Range 0.5 Hz to 32 kHz
Resolution 24-bit
Absolute Accuracy +/-0.01% (2000-32000 Hz), +/-0.1% (0.5-2000 Hz)
Duty Cycle Support 20-80% or >=10 us pulse width
Maximum Voltage +/-33 VDC
Gear Teeth Support 1 to 255 teeth
Diagnostic Features Precision reference test
Minimum Update Rate 20 ms
Isolation Rating >=500 VDC functional to earth

Triple Modular Redundancy (TMR) and Fail-Safe Execution

The module processes incoming pulse transitions across three independent channels to execute triple modular redundancy (TMR) algorithms. Channel-to-channel galvanic isolation rating at >=500 VDC suppresses field signal cross-talk and blocks high-voltage noise spikes from penetrating the central system bus. Integrated internal diagnostic routines continuously execute precision reference tests, isolating channel discrepancies and forcing a fail-safe state execution without interrupting active turbine overspeed or machinery protection functions.

Frequently Asked Questions

Q: Can the P13381 pulse input module be replaced online without powering down the Tricon rack?

A: Yes, online hot-replacement is supported. The module can be extracted and inserted into a live chassis slot without interrupting active logic execution or tripping safety protection loops.

Q: How does the module handle signal conditioning for passive magnetic pick-ups versus active sensors?

A: The module accommodates differential or single-ended signal configurations across its 6 input channels, processing both non-amplified magnetic pick-ups and active open-collector inputs within a +/-33 VDC maximum threshold.

Field Installation Guidelines

Observe strict electrostatic discharge precautions when handling the module. Slide the card into the designated Tricon baseplate slot until the rear connectors lock firmly into the backplane, and tighten all retaining screws to establish frame grounding. Run field sensor wiring through shielded twisted-pair cables, routing signal conduits away from high-voltage AC lines. Terminate cable shields directly at the system earth ground bar to maintain signal integrity and prevent electromagnetic interference.