Triconex Tricon P13381 Pulse Input Module
Manufacturer: Triconex
-
Part Number: PI3381
Condition:New with Original Package
Product Type: Pulse Input Modules
-
Country of Origin: USA
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
Triconex P13381 Pulse Input Module
The Triconex P13381, also cataloged as the P13381 Pulse Input Module, operates as a dedicated hardware component for capturing speed and frequency measurements from rotating machinery sensors within Triconex Tricon Safety Instrumented System platforms.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | P13381 |
| Brand | Triconex |
| Origin | USA |
| Weight | Standard Chassis Module Weight |
| Dimensions | Standard Tricon Chassis Slot Format |
| Operating Temp | -20 to +65 deg C |
| Power Consumption | System Backplane Powered |
| Product Type | Pulse Input Modules |
| System Compatibility | Triconex Tricon Safety Instrumented System |
| Input Channels | 6 pulse inputs, channel isolated |
| Sensor Types | Magnetic, active, open collector |
| Input Configuration | Differential or single-ended |
| Speed Measurement Range | 0 to 32000 RPM |
| Input Frequency Range | 0.5 Hz to 32 kHz |
| Resolution | 24-bit |
| Absolute Accuracy | +/-0.01% (2000-32000 Hz), +/-0.1% (0.5-2000 Hz) |
| Duty Cycle Support | 20-80% or >=10 us pulse width |
| Maximum Voltage | +/-33 VDC |
| Gear Teeth Support | 1 to 255 teeth |
| Diagnostic Features | Precision reference test |
| Minimum Update Rate | 20 ms |
| Isolation Rating | >=500 VDC functional to earth |
Triple Modular Redundancy (TMR) and Fail-Safe Execution
The module processes incoming pulse transitions across three independent channels to execute triple modular redundancy (TMR) algorithms. Channel-to-channel galvanic isolation rating at >=500 VDC suppresses field signal cross-talk and blocks high-voltage noise spikes from penetrating the central system bus. Integrated internal diagnostic routines continuously execute precision reference tests, isolating channel discrepancies and forcing a fail-safe state execution without interrupting active turbine overspeed or machinery protection functions.
Frequently Asked Questions
Q: Can the P13381 pulse input module be replaced online without powering down the Tricon rack?
A: Yes, online hot-replacement is supported. The module can be extracted and inserted into a live chassis slot without interrupting active logic execution or tripping safety protection loops.
Q: How does the module handle signal conditioning for passive magnetic pick-ups versus active sensors?
A: The module accommodates differential or single-ended signal configurations across its 6 input channels, processing both non-amplified magnetic pick-ups and active open-collector inputs within a +/-33 VDC maximum threshold.
Field Installation Guidelines
Observe strict electrostatic discharge precautions when handling the module. Slide the card into the designated Tricon baseplate slot until the rear connectors lock firmly into the backplane, and tighten all retaining screws to establish frame grounding. Run field sensor wiring through shielded twisted-pair cables, routing signal conduits away from high-voltage AC lines. Terminate cable shields directly at the system earth ground bar to maintain signal integrity and prevent electromagnetic interference.