TZN124-EX TZN124 HIMA Safety Input Module
Manufacturer: HIMA
-
Part Number: TZN124-EX
Condition:New with Original Package
Product Type: Analog Input Modules
-
Country of Origin: Germany
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
HIMA TZN124-EX Safety-Related Input Module
Configured for precise analog signal acquisition from 2-wire transmitters in safety instrumented systems, the HIMA TZN124-EX (TZN124 Safety-Related Input Module) provides direct physical/electrical execution.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | TZN124-EX |
| Brand | HIMA |
| Origin | Germany |
| Weight | 0.2 kg |
| Dimensions | 128 x 165 x 130 mm |
| Operating Temp | -25 to 70 deg C |
| Power Consumption | 24 VDC nominal transmitter supply excitation |
| Input Signal | 2-wire transmitter signals (pressure, temperature, flow) |
| Signal Processing | Optional square-root extraction for differential pressure flow |
| Electrical Isolation | Full galvanic isolation between input, output, and power circuits |
| Mounting | Rack or panel installation |
Galvanic Isolation and Fail-Safe State Execution
The safety-related input hardware implements complete galvanic isolation across input channels, output stages, and internal power rails to suppress ground loops and eliminate common-mode signal interference. Upon detection of open field loops or out-of-range sensor drift, internal diagnostic routines force the module logic into a predetermined fail-safe state. This architecture prevents unconditioned signal corruption from propagating across safety instrumented system backplanes during critical process shutdowns.
Frequently Asked Questions
Q: Does the input channel supply power directly to field transmitters?
A: Yes, the module provides 24 VDC loop excitation power directly to connected 2-wire pressure, temperature, or flow transmitters.
Q: How does the module handle differential pressure flow measurements?
A: The onboard signal conditioning circuitry incorporates optional square-root extraction logic to linearize flow calculations directly before logic transfer.
Field Installation Guidelines
Follow these core procedures to maintain signal integrity and ensure safe operation:
- Mount the module securely into the designated rack slot or enclosure panel using appropriate mounting hardware.
- Route 2-wire field transmitter wiring separately from high-voltage AC distribution circuits to prevent inductive noise coupling.
- Terminate shielded signal wiring at the dedicated cabinet earth bus using short, low-impedance grounding conductors.
- Verify that total loop impedance on the 2-wire field circuit remains within limits to guarantee adequate 24 VDC transmitter supply excitation.