VE4035S2B1 KJ3221X1-BA1 Emerson DeltaV Series 2 Analog Input Module
VE4035S2B1 KJ3221X1-BA1 Emerson DeltaV Series 2 Analog Input Module
VE4035S2B1 KJ3221X1-BA1 Emerson DeltaV Series 2 Analog Input Module
/ 3

VE4035S2B1 KJ3221X1-BA1 Emerson DeltaV Series 2 Analog Input Module

  • Manufacturer: Emerson

  • Part Number: VE4035S2B1 KJ3221X1-BA1

  • Condition:New with Original Package

  • Product Type: Analog Input Modules

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Emerson VE4035S2B1 DeltaV Series 2 Analog Input Module

The Emerson VE4035S2B1, also cataloged as the KJ3221X1-BA1 Analog Input Module, operates as a dedicated hardware component for 16-channel analog signal acquisition within Emerson DeltaV DCS platforms.

Hardware Specifications

Parameter Specification
Model VE4035S2B1 (Part Number: KJ3221X1-BA1 / KJ3221X1-EA1)
Brand Emerson
Origin USA
Weight 0.20 kg
Dimensions 51 x 102 x 102 mm
Operating Temp -40 to +70 deg C
Power Consumption 12 VDC at 150 mA (LocalBus), 12 VDC at 300 mA (Bussed Field Power)
System Compatibility Emerson DeltaV DCS
Number of Channels 16 isolated analog inputs
Signal Range 4-20 mA current input
Resolution 16-bit analog-to-digital conversion
HART Support Pass-through, point-to-point only
Field Circuit Rating 24 VDC at 32 mA
Protection Class IP20
Airborne Contaminants ISA-S71.04 Class G3
Shock Resistance 10 g half-sine wave for 11 ms
Vibration Resistance 1 mm peak-to-peak (2-13.2 Hz), 0.7 g (13.2-150 Hz)
Certifications CE, UL, ATEX, IECEx (Zone 2 / Class I Div. 2)

Process Control and Signal Isolation Features

The module delivers 16-bit resolution across 16 channels, enabling continuous acquisition of 4-20 mA HART loop protocol signals from field transmitters. Integrated channel-to-channel isolation prevents differential ground loops from corrupting measurement values or propagating transient voltage noise to the LocalBus logic carrier. Internal cold junction compensation (CJC) routing on adjacent baseplates supports stable temperature conversions, maintaining loop calibration integrity across high-density industrial control cabinets.

Frequently Asked Questions

Q: What are the primary backplane current draws for the VE4035S2B1 module?

A: The module draws 12 VDC at 150 mA from the internal LocalBus rail and 12 VDC at 300 mA from the bussed field power connection, delivering up to 24 VDC at 32 mA per field circuit.

Q: Does the VE4035S2B1 support hot-swappable replacement on active DeltaV baseplates?

A: Engineers can perform hot-swappable installation and removal of the module on energized DeltaV I/O baseplates without disrupting adjacent I/O slots or interrupting backplane communication.

Field Installation Guidelines

  1. Seat the module firmly onto the designated DeltaV carrier slot until the top and bottom mechanical latches click into place.
  2. Route all 4-20 mA field transmitter wiring through shielded twisted-pair cables to preserve 16-bit analog-to-digital conversion accuracy.
  3. Terminate signal cable shields at a single point on the cabinet instrument ground bar to prevent circulating ground currents.
  4. Maintain physical separation between 24 VDC analog input field wiring and high-voltage AC power cables in cabinet wireways.