Yokogawa ADV159-P01 S1 CENTUM VP Digital Input Module
Yokogawa ADV159-P01 S1 CENTUM VP Digital Input Module
Yokogawa ADV159-P01 S1 CENTUM VP Digital Input Module
/ 3

Yokogawa ADV159-P01 S1 CENTUM VP Digital Input Module

  • Manufacturer: Yokogawa

  • Part Number: ADV159-P01 S1

  • Condition:New with Original Package

  • Product Type: Digital Input Modules

  • Country of Origin: Japan

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Yokogawa ADV159-P01 Digital Input Modules

The Yokogawa ADV159-P01 S1 serves as the primary ADV159 Digital Input Module utilized to execute digital field signal acquisition across Yokogawa CENTUM VP, CENTUM CS, and ProSafe-RS platforms.

Suffix Breakdown & Model Matrix

Base Model Suffix / Option Code Description / Specification
ADV159 -P01 Standard digital input module configuration
  S1 ISA Standard G3 conformal coating option for environmental protection

Hardware Specifications

Parameter Specification
Model ADV159-P01 S1 (Base Model: ADV159)
Brand Yokogawa
Origin Japan
Weight 0.4 kg
Dimensions Standard Yokogawa CENTUM VP subrack module form factor
Operating Temp -10 to +55 deg C
Power Consumption Standard backplane power allocation
Input Channels 16 channels (S1 configuration)
Rated Input Voltage 24 to 250 VDC
Input ON Voltage 11 to 250 VDC
Input OFF Voltage 0 to 10 VDC
Typical Input Current 4.7 mA per channel at 120 VDC
Signal Isolation Channel-to-channel and channel-to-system optical isolation
Withstanding Voltage 2 kV AC for 1 minute (signal to system); 1.35 kV AC between channels

Process Control & Channel-to-Channel Isolation Architecture

Yokogawa CENTUM VP and ProSafe-RS architectures employ comprehensive optical isolation stages to insulate high-density digital input channels from field noise and voltage spikes. The individual channel isolation scheme isolates incoming DC control loops across a wide 24 to 250 VDC potential band. This galvanic isolation prevents common-mode noise transfer into core processing logic and maintains signal integrity across distributed field instrumentation without cross-channel coupling.

Frequently Asked Questions

Q: How does the S1 suffix alter the module environmental specification?

A: The S1 suffix designates compliance with ISA Standard G3 conformal coating guidelines, providing physical protection against corrosive gas atmospheres.

Q: Can this module operate within a dual-redundant I/O subrack slot pair?

A: Yes, the module supports dual-redundant subrack configurations to maintain continuous signal processing if one card experiences hardware interruption.

Field Installation Guidelines

Ensure main subrack power and field loop supplies are disconnected prior to inserting or removing the module from the baseplate slot.

When landing field wiring on terminal panels, maintain separate cable trays for high-voltage DC field inputs and low-level analog or communication cables to minimize cross-talk. Ground all cable shields at a single dedicated system earth busbar within the cabinet.

Verify that the module subrack locking mechanism fully engages during mounting to maintain positive electrical contact along the system backplane bus.