Yokogawa SAI143-S53 S1/A4S10 16-Bit Analog Safety Card
Yokogawa SAI143-S53 S1/A4S10 16-Bit Analog Safety Card
Yokogawa SAI143-S53 S1/A4S10 16-Bit Analog Safety Card
/ 3

Yokogawa SAI143-S53 S1/A4S10 16-Bit Analog Safety Card

  • Manufacturer: Yokogawa

  • Part Number: SAI143-S53/A4S10

  • Condition:New with Original Package

  • Product Type: Analog Input Modules

  • Country of Origin: Japan

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Product Description

Safety-Critical Analog Signal Acquisition

The Yokogawa SAI143-S53/A4S10 is a high-integrity Analog Input Module designed specifically for the ProSafe-RS Safety Instrumented System (SIS). As a vital component of the Field Control Station (FCS), this module provides 16 channels of isolated analog inputs, facilitating the monitoring of critical process variables such as pressure, temperature, and level. The SAI143-S53 is engineered to meet stringent SIL3 safety requirements, ensuring reliable data acquisition for emergency shutdown (ESD) and fire and gas (F&G) applications.

Enhanced Reliability with A4S10 Terminal Interface

This specific configuration features the SAI143-S53 module bundled with the A4S10 terminal block assembly. The A4S10 provides a robust physical interface for field wiring, supporting high-density industrial cabling with secure pressure-clamp or screw connections. The module supports dual-redundancy, allowing two units to operate in parallel to ensure continuous process visibility. With 16-bit A/D resolution and galvanic isolation of 1500 V AC, the SAI143-S53/A4S10 maintains signal precision even in environments with significant electromagnetic interference.

Detailed Technical Specifications

The following table details the technical performance and mechanical specifications of the SAI143-S53/A4S10.

Feature Specification Details
Manufacturer Yokogawa
Model Number SAI143-S53
Terminal Block A4S10 (Included Interface)
Input Channels 16 Channels, Fully Isolated
Signal Range 4 to 20 mA DC (Standard)
Permissible Range 0 to 25 mA DC
A/D Resolution 16-bit
Accuracy ±16 µA (Input range 1 to 23 mA)
Data Update Cycle 40 ms
Input Impedance 250 Ω (Power-ON); ≥500 kΩ (Power-OFF)
Temperature Drift ±16 µA per 10 °C
Isolation Voltage 1500 V AC (Field to System)
Redundancy Dual redundant configuration supported
Operating Temp 0 °C to +60 °C
Weight 0.7 kg
Origin Japan

 