GE IS200TRLYH1BGG Relay Terminal Board | Speedtronic Control
Manufacturer: GE Fanuc
-
Part Number: IS200TRLYH1BGG
Condition:New with Original Package
Product Type: Relay Terminal Board
-
Country of Origin: USA
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
GE IS200TRLYH1BGG – Product Description
Overview
The GE IS200TRLYH1BGG Relay Output Terminal Board is a robust interface module for the Mark VI Speedtronic turbine control system. It provides reliable connection between turbine control logic and high-power external devices, including solenoids, fuel valves, ignition transformers, alarms, and breakers. Moreover, its hot-swappable design and fast response time make it ideal for critical turbine applications, reducing maintenance downtime significantly.
Technical Specifications
Relay Configuration
-
12 Form-C plug-in magnetic latching relays
-
Each channel independently replaceable
Contact Ratings
-
2 A @ 125 VDC (resistive load)
-
3 A @ 120/240 VAC (resistive load)
-
0.6 A @ 125 VDC (inductive load)
Coil Drive Voltage
-
Selectable 24 VDC or 125 VDC (jumper configurable)
Response Time
-
Trip output ~10 ms
Protection Features
-
MOV surge suppression
-
Freewheeling diode for transient protection
-
6 fused branches, 1 unfused
-
1500 Vrms isolation between channels
Hot-Swap Capability
-
Euro-block terminals for online relay group replacement
-
EEPROM auto-downloads parameters during swap (3minutes)
Environmental Ratings
-
Operating temperature: –40 °C to +70 °C
-
Storage temperature: –40 °C to +85 °C
Physical Dimensions
-
178 mm × 330 mm
-
Weight: 0.5 kg
-
Country of Origin: United States
FAQ
Q1: Is this board compatible with the Mark VI Speedtronic system?
Yes, the IS200TRLYH1BGG is specifically designed for integration with GE Mark VI turbine controllers.
Q2: Can individual relays be replaced in the field?
Yes. Each Form-C relay channel is independently replaceable without removing the full board.
Q3: How quickly does the board respond to overspeed or vibration events?
Trip output responds within approximately 10 milliseconds for rapid turbine protection.
Q4: Does it support hot-swapping?
Yes. Relay groups can be replaced online with EEPROM auto-configuration to minimize downtime.
Q5: What environmental conditions can the board handle?
It operates between –40 °C to +70 °C and is designed for harsh industrial turbine environments.