UR600IR/BGT by ABB | High-Spec Infrared Flame Sensor
Manufacturer: ABB
-
Part Number: UR600IR/BGT
Condition:New with Original Package
Product Type: High-Spec Infrared Flame Sensor
-
Country of Origin: Sweden
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
ABB UR600IR/BGT Infrared Flame Scanner — Product Description
Overview
The ABB UR600IR/BGT is an industrial infrared flame scanner built for dependable burner monitoring in large combustion systems. It belongs to ABB’s Uvisor flame-detection platform, which supports safe boiler operation across power generation and heavy-process industries. Moreover, its PbS sensor captures flame flicker in the 600–3000 nm infrared spectrum, allowing operators to evaluate combustion stability with strong accuracy and minimal interference.
The detector features a rugged enclosure and ATEX-certified construction, therefore ensuring safe performance in hazardous areas. In addition, continuous self-checking enhances system reliability by verifying sensor health during every operating cycle. Plants adopting mixed-fuel or variable-load combustion processes rely on this model for consistent signal quality and long-term service life.
Technical Specifications
-
Model: UR600IR/BGT
-
Product Type: Infrared flame scanner
-
Manufacturer: ABB
-
Condition: New with original package
-
Sensor Type: PbS (lead sulfide) infrared sensor
-
Spectral Sensitivity: 600–3000 nm
-
Power Consumption: ~300 mW DC (supplied through Uvisor MFD)
-
Operating Temperature: –10 °C to +85 °C
-
Storage Temperature: –40 °C to +100 °C
-
Max Continuous Temperature (fiber extension): 350 °C
-
Protection Class: IP66 / NEMA 4X
-
Hazardous Rating: EEx-d IIC T6, ATEX certified
-
Dimensions: 94 × 94 × 172 mm
-
Weight: 1 kg
-
Air Purge Requirement: 115 l/min (4 SCFM)
-
Country of Origin: USA
-
Payment Options: T/T, Western Union
-
Shipping Port: Xiamen
FAQ
Q1: What sensing technology is used in the UR600IR/BGT?
It uses a PbS infrared sensor that detects flame flicker within the 600–3000 nm range.
Q2: Does the detector include self-checking capability?
Yes, the unit performs continuous internal self-checking to enhance operational safety.
Q3: Can the scanner operate in high-temperature zones?
Yes, a fiber-optic extension allows deployment in areas reaching 350 °C.
Q4: Which controller analyzes the flame signal?
The Uvisor MFD unit evaluates signal amplitude and frequency to confirm flame presence.
Q5: Is the UR600IR/BGT certified for hazardous environments?
Yes, it carries ATEX and EEx-d IIC T6 approvals suitable for industrial boiler areas.