Bachmann DPM200 | High-Speed PROFIBUS DP Interface
Manufacturer: Bachmann
-
Part Number: DPM200
Condition:New with Original Package
Product Type: High-Speed PROFIBUS DP Interface
-
Country of Origin: Austria
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
Bachmann DPM200 | PROFIBUS DP Communication Module
Product Description
The Bachmann DPM200 is a versatile PROFIBUS® DP communication module designed for industrial automation networks. It can operate as a DP Master, DP Slave, or in combined master/slave mode, making it ideal for multi-master network configurations.
Integrated into the Bachmann M1 automation system, the DPM200 provides seamless communication between PLCs, DCS systems, and field devices like sensors and actuators. Dual 9-pin D-Sub connectors with RS-485 signal levels allow redundant bus topologies and high fault tolerance.
With 8 kByte of shared memory, the module enables efficient data exchange and works with third-party engineering tools through standardized interfaces. It is built for harsh industrial environments, featuring 500 V electrical isolation, IP40 protection, and a wide operating temperature range.
Technical Specifications
| Specification | Details |
|---|---|
| Model Number | DPM200 |
| Function | PROFIBUS® DP Master/Slave Communication Module |
| Protocol | PROFIBUS DP V0 (EN 50170 compliant) |
| Operating Modes | DP Master, DP Slave, Combined Master/Slave |
| Transmission Speed | 9.6 Kbaud to 12 Mbaud (auto-adaptive) |
| Process Data Image | 8 kByte shared memory |
| Interfaces | 2 × 9-pin D-Sub connectors (RS-485 signal level) |
| Electrical Isolation | 500 V between fieldbus and controller |
| Power Consumption | 400 mA @ 5 VDC |
| Operating Temperature | –30°C to +60°C (standard); –40°C to +85°C (cold climate version) |
| Humidity Range | 5% to 95% (non-condensing) |
| Protection Class | IP40 |
| Certifications | CE, cULus, CCC |
| Country of Origin | Austria |
FAQ
Q1: Can the DPM200 operate as both master and slave simultaneously?
A1: Yes, it supports combined master/slave mode in multi-master networks.
Q2: What communication protocol does it support?
A2: The DPM200 supports PROFIBUS DP V0, compliant with EN 50170.
Q3: What is the maximum transmission speed?
A3: It supports speeds from 9.6 Kbaud up to 12 Mbaud, auto-adaptive.
Q4: Is it suitable for harsh industrial environments?
A4: Yes, with 500 V electrical isolation, IP40 protection, and wide temperature tolerance.
Q5: How is the module connected to the network?
A5: Via 2 × 9-pin D-Sub connectors with RS-485 signal levels for redundancy.