Description / Product Summary
The GE Fanuc Emerson IC695MDL664CA is a smart digital input module designed for demanding industrial environments that require reliable signal detection and advanced diagnostics. Each input point provides clear feedback to the PACSystems RX3i controller, ensuring accurate process monitoring across complex automation systems. Moreover, the module’s diagnostic features help maintenance teams identify wiring issues early, which improves system uptime and long-term reliability. In addition, its rugged construction supports applications where stable 24 VDC input monitoring is essential.
Technical Specifications
Input Channels
-
16 diagnostic digital inputs
-
Positive logic (ON when voltage applied)
Input Voltage
-
Nominal: 24 VDC
-
Range: 20–30 VDC
-
ON threshold: >0.5 × VIN
-
OFF threshold: <0.2 × VIN
Input Speed
-
Selectable response times: 0.5 ms to 100 ms
Diagnostics
-
Open-wire detection
-
Short-circuit and fault reporting
-
LED indicators for module and channel health
Power Requirements
-
225 mA @ 5 VDC
-
95 mA @ 3.3 VDC
Physical Specifications
-
Dimensions: 141.4 × 264.9 × 147.3 mm
-
Weight: 0.8 kg
-
Single-slot RX3i rack mount
Certifications
-
UL 508, CSA C22.2
-
Hazardous locations: Class I, Div 2
Environmental Ratings
-
Operating: 0 °C to +60 °C
-
Storage: –40 °C to +85 °C
-
Humidity: 5–95% non-condensing
FAQ
Q1: Does the IC695MDL664CA support diagnostics on every input?
Yes, each channel offers advanced diagnostics including open-wire and fault detection.
Q2: Can I adjust the input response time?
Yes, you can select response times between 0.5 ms and 100 ms depending on your application.
Q3: Is this module suitable for hazardous locations?
Yes, it carries Class I, Division 2 approvals for industrial hazardous areas.
Q4: Does it require a specific RX3i rack type?
It uses a standard single-slot position within any compatible PACSystems RX3i base.
Q5: What voltage range does it accept?
The module accepts 20–30 VDC with 24 VDC nominal input.