Product Overview
The Yokogawa NFAI543-S50 is a 16-channel analog output module designed for ProSafe-RS safety instrumented systems (SIS). It provides isolated current outputs (4–20 mA) to field devices such as control valves, actuators, and transmitters, ensuring reliable operation in high-integrity industrial applications.
This module supports HART communication, enabling advanced diagnostics, remote configuration, and monitoring. Each channel features fallback options, either HOLD to maintain the last value or SETV to move to a predefined value in case of faults. The unit requires a 24 V DC field power supply and ensures robust isolation between system and field wiring.
Technical Specifications
Specification | Details |
---|---|
Model | NFAI543-S50 |
Type | Analog Output Module |
Channels | 16 isolated current output channels |
Signal Range | 4–20 mA DC |
Fallback Options | HOLD or SETV per channel (fallback detection time: 4 seconds) |
Power Supply | 24 V DC field power required |
HART Support | Yes – refer to GS 34P02Q53-01E |
Isolation Voltage | Up to 500 V AC (cable dependent) |
System Compatibility | ProSafe-RS SIS |
Connector Type | MIL connector (voltage rating depends on cable used) |
Weight | 0.6 kg |
Applications | Safety instrumented systems, industrial automation, process control |
Condition | New, original package |
Shipping Port | Xiamen |
FAQ
Q1: Is the NFAI543-S50 compatible with HART devices?
A1: Yes, it fully supports HART communication, enabling advanced diagnostics and configuration.
Q2: How many output channels does this module provide?
A2: The NFAI543-S50 offers 16 isolated 4–20 mA current output channels.
Q3: What are the fallback options for channel failures?
A3: Each channel can operate in HOLD mode (maintain last value) or SETV mode (predefined value).
Q4: What power supply does the module require?
A4: The module requires a 24 V DC field power supply for proper operation.
Q5: Can it be used in harsh industrial environments?
A5: Yes, it provides robust isolation and reliable operation for safety-critical systems.