CI871AK01 ABB | Industrial PROFINET Communication Module
Manufacturer: ABB
-
Part Number: CI871AK01
Condition:New with Original Package
Product Type: Industrial PROFINET Communication Module
-
Country of Origin: Sweden
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
Product Overview
The ABB CI871AK01 is a high-performance PROFINET IO interface module designed for ABB AC 800M control systems.
It acts as a gateway between the AC 800M controller and field devices, providing deterministic real-time communication and robust data exchange.
Engineered for demanding industrial environments, the CI871AK01 supports system and network redundancy, ensuring high availability and seamless integration in distributed control applications.
Its compatibility with Control Builder M and System 800xA makes configuration straightforward and reduces system downtime.
Technical Specifications
Specification | Details |
---|---|
Model Number | CI871AK01 (CI871A) |
Article Number | 3BSE092693R1 |
Product Type | PROFINET IO Interface Module |
System Compatibility | ABB AC 800M / S800 I/O |
Communication Protocol | PROFINET IO (Master) |
Supported Standards | IEEE 802.3, IEC 61158 |
Ethernet Ports | 2 × RJ45 (only CH1 for PROFINET IO) |
Baud Rate | 100 Mbps (full duplex) |
Redundancy Support | Yes – system and network redundancy |
Diagnostics | Built-in self-diagnostics with LED indicators |
Addressing Methods | DHCP, DCP, manual configuration |
Configuration Tool | Control Builder M |
Power Supply | +24 VDC via CEX-Bus |
Mounting Baseplate | TP867 |
OS Compatibility | System 800xA 6.0.3.3, 6.1.1 and later |
Dimensions (W × H × D) | 127.5 × 186 × 59 mm |
Weight | 0.7 kg |
RoHS Compliance | EU Directive 2011/65/EU |
WEEE Category | 5. Small Equipment |
Country of Origin | Switzerland |
FAQ
Q1: What is the main function of the ABB CI871AK01?
A1: It acts as a PROFINET IO interface module, connecting AC 800M controllers with field devices.
Q2: How many Ethernet ports are available?
A2: The module features 2 RJ45 ports, with only CH1 used for PROFINET IO communication.
Q3: Does the module support redundancy?
A3: Yes, it supports both system and network redundancy for high availability.
Q4: What voltage does it require?
A4: It operates at +24 VDC via CEX-Bus.
Q5: What industrial software is compatible for configuration?
A5: The Control Builder M tool and System 800xA (6.0.3.3, 6.1.1 or later) are compatible.