MET148‑2 Schneider | 8 RTD Input Sensor Module for Sepam Relays
MET148‑2 Schneider | 8 RTD Input Sensor Module for Sepam Relays
MET148‑2 Schneider | 8 RTD Input Sensor Module for Sepam Relays
/ 3

MET148‑2 Schneider | 8 RTD Input Sensor Module for Sepam Relays

  • Manufacturer: Schneider

  • Part Number: MET148-2

  • Condition:New with Original Package

  • Product Type: 8 RTD Input Sensor Module for Sepam Relays

  • Country of Origin: France

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Product Description

Overview

The Schneider MET148‑2 is an external temperature sensor module designed for Sepam Series 20, 40, and 80 protection relays. It allows direct temperature measurement using Resistance Temperature Detectors (RTDs) such as Pt100, Ni100, and Ni120. Moreover, this module can be connected during installation, commissioning, or maintenance, providing flexible integration with existing protection systems. The compact, screw-terminal design ensures quick installation without additional power supplies, as it is powered directly by the Easergy P5 relay.

Technical Specifications

Sensor Inputs

  • Quantity: 8 RTD inputs

  • Supported RTD Types: Pt100, Ni100, Ni120

  • Connection: Screw-type terminals

  • Wiring: 3-wire configuration

  • Auxiliary Power: Powered by Easergy P5, no external supply required

Mechanical Dimensions & Weight

  • Height: 88 mm (3.46 in)

  • Width: 144 mm (5.70 in)

  • Depth: 30 mm (1.18 in)

  • Net Weight: 200 g (0.44 lbs)

Environmental & Compliance

  • Operating Temperature: 0–55 °C

  • Storage Temperature: −40–85 °C

  • Relative Humidity: 5–95%, non-condensing

  • Certifications: RoHS, REACh, IEC standards, UL, Marine certification

Lifecycle & Support

  • End of Commercialization: June 2024

  • Service Support: Available until December 31, 2030

  • Recommended Replacement: Schneider PowerLogic™ P5 protection relays

FAQ

Q1: Which Sepam series relays are compatible with MET148‑2?
The MET148‑2 works with Sepam Series 20, 40, and 80 protection relays.

Q2: How many RTD inputs does the module provide?
It provides 8 RTD inputs for Pt100, Ni100, and Ni120 sensors.

Q3: Does the module require an external power supply?
No, it is powered directly by the connected Easergy P5 relay.

Q4: Can it be installed during maintenance?
Yes, the module can be connected at installation, commissioning, or maintenance stages.

Q5: What certifications does the module have?
It is compliant with EN 60255-26, EN 60255-27, UL standards, and carries marine certification.

Anda mungkin juga menyukainya